Physical Location
The controller is designed for limited front access (components may have to be
removed) and should be installed with adequate and safe clearance to allow for
total door opening. The back of the unit may be placed against a wall and several
units may be set end to end. In special cases where floor space is limited and the
unit is not against a wall, certain cabinet sections may be placed back to back.
This requirement must be stated in the specifications in order to mechanically
alter the controller.
Ground Bus Bar
Controllers which are delivered in two (or more) sections, or retrofit controllers,
will require that the ground bus bar (10 x 51 mm) [0.375 x 2 in.], which runs the
entire length of the equipment in the center back side, be reconnected. A
mechanical lug for #8-#10 AWG or #6-250 MCM cable is supplied at the
incoming end of the line-up. When the sections are brought together, bus links
are used to connect the bus bars.
Power and Control Wiring
Controllers consisting of two or more sections will require that the power and
control wiring be connected per the schematic drawings provided.
Control Cables
Control cable entry/exit should be located near the terminal blocks; customer’s
connections are to be routed along the empty side of the terminals. Nylon cable
tie loops are provided at the left, front corner of the cabinet to route control
cables safely behind the low voltage panel hinges. Cables should be routed so they
do not interfere with the swing of the low-voltage panels.
TIP
Rockwell Automation can assist with the selection of an appropriate
interlocking method, which may include mechanical modifications to the
cabinet(s) or key-type lock systems.
TIP
An auxiliary cabinet may be attached to the main structure. It will be ram-
interlocked with the main power cell door, which will not allow it to be opened
until the main power cell door is opened.
IMPORTANT
Refer to 2-high, Series B drawings in Publication
ground bus connection.
Summary of Contents for SMC-50
Page 10: ...10 Rockwell Automation Publication 1560F UM001A EN P June 2019 Table of Contents Notes ...
Page 12: ...12 Rockwell Automation Publication 1560F UM001A EN P June 2019 Preface Notes ...
Page 68: ...68 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 2 Installation Notes ...
Page 120: ...120 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 4 Programming Notes ...
Page 130: ...130 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 5 Metering Notes ...
Page 156: ...156 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 8 Diagnostics Notes ...
Page 198: ...198 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 10 Maintenance Notes ...
Page 284: ...284 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix H Spare Parts Notes ...
Page 286: ...286 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix I Accessories Notes ...
Page 291: ......