Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
37
Product Overview
Chapter 1
Status Indication
All auxiliary contacts can be programmed as NO or NC. The contact without a
suffix indicates a NO state (Normal). A contact followed by NC indicates a
normally closed state (Normal NC).
Figure 20 - Control Terminals - SMC-50 Control Module
• The Aux #1 contact is always programmed for External Bypass (NO) to
control the bypass contactor in MV applications.
• The Aux #2 contact is always configured as Normal (NO) to control the
line contactor for MV applications.
• In1 DC is typically programmed for Emergency Run in MV Applications
Figure 21 - Control Terminals - 150-SM4 Digital I/O Card (Slot 7)
• Input #A1 is typically programmed for ‘Start’ in MV applications.
• Input #A2 is typically programmed for ‘Stop Option’ in MV applications.
• Input #A3 is typically programmed for ‘Coast’ in MV applications.
• Aux #A1 is typically programmed for ‘Fault’ in MV applications.
State
Description
Normal/Normal NC
The contact state changes when the unit receives a Start/Stop signal.
Up-to-Speed/Up-to-Speed NC
The contact state changes when the motor approaches rated speed.
Alarm/Alarm NC
The contact state changes when an Alarm condition is detected.
Fault/Fault NC
The contact state changes when a Fault condition is detected.
Network Control/Network Control NC The contact state is controlled over the network. (Refer to
Module—Bit Identification on page 140
, which describes logic command
word to control auxiliary outputs).
External Bypass
This contact controls the Bypass contactor for MV applications.
External Brake
The contact state changes when the external braking command is active and
opens when it is not active Aux. Control: The contact state changes when an
auxiliary output is configured for Aux. Control.
+L1
-L2
12
11
10
9
8
7
5
6
4
2
1
3
Control Power and
Ground
In
te
rnal
+2
4V
DC
In
1 DC
In
2 DC
En
ab
le
I/O
In
te
rn
al DC
Co
m
m
on
Aux 2
Aux 1
Control Module Standard I/O
NC
A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12
AC Inputs
Auxiliary Relay Outputs
150-SM4 Option I/O Module
AuxA2
AuxA1
AuxA3
In
A2
In
A3
In
A1
In
A4
In
CO
M
Summary of Contents for SMC-50
Page 10: ...10 Rockwell Automation Publication 1560F UM001A EN P June 2019 Table of Contents Notes ...
Page 12: ...12 Rockwell Automation Publication 1560F UM001A EN P June 2019 Preface Notes ...
Page 68: ...68 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 2 Installation Notes ...
Page 120: ...120 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 4 Programming Notes ...
Page 130: ...130 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 5 Metering Notes ...
Page 156: ...156 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 8 Diagnostics Notes ...
Page 198: ...198 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 10 Maintenance Notes ...
Page 284: ...284 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix H Spare Parts Notes ...
Page 286: ...286 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix I Accessories Notes ...
Page 291: ......