18
ProcessLogix and ControlLogix System Redundancy Module
Publication
1757-IN092E-EN-P - November 2007
Flash Upgrade the Modules
To flash upgrade the modules to the latest firmware revision, perform this
procedure.
1.
Go to http://support.rockwellautomation.com and download the
latest firmware revision for your 1757-SRM module.
2.
Download and install the ControlFLASH Firmware Upgrade Kit.
3.
Apply power to only one redundant chassis.
4.
Wait for the module to roll display: FACT BOOT FLSH UPDT
REQD.
5.
Start your ControlFLASH Firmware Upgrade Kit and apply the latest
firmware to the module.
For additional information on identifying and upgrading your
1757-SRM module, see the ControlFLASH Firmware Upgrade Kit
Quick Start, publication 1756-QS105.
6.
Verify that the module displays PRIM, indicating a successful flash
upgrade.
7.
Turn off the power to the redundant chassis used in step 3.
8.
Apply power to the other redundant chassis.
IMPORTANT
Back up any programs or data that you have saved to a device.
When you upgrade firmware, all old data will be overwritten.
IMPORTANT
Make sure you know the serial number from your original
firmware disk. To upgrade to the latest firmware revision,
such as 4.
x
, you will need to provide the original serial
number. If you don’t have the serial number, refer to
Rockwell Automation Support on the back cover.