PowerFlex Active Front End in IP20 2500 MCC Style Enclosure Frame 13 Right-Side Bus Splice Kit

 

 

Step 4: Connect the MCC bus and PE ground splices to the AFE bus and ground 

bars, respectively.

a.

Assemble the MCC bus splices to the AFE horizontal bus bars using 
the supplied hardware.
Torque to 300 ±10% in

lb (33.9 ±10% N

M).

b. Assemble the PE ground splices to the AFE top and bottom PE 

ground bus bars using the supplied hardware.
Torque to 65.0 ±10% in

lb (7.3 ±10% N

M).

Hex Nut, Conical Spring Washer
29360-527-01
16 Places (

8

 are used to connect

to MCC bus in adjacent enclosure)

Hex Flange Screw
29171-640-02

8

 Places (4 are used to connect

to PE bus in adjacent enclosure)

PE Ground Splice
PN-226139
2 Places

Bus Clamp Assembly
40319-400-05

8

 Places (4 are used to connect

to MCC bus in adjacent enclosure)

Flat Washer
M-353
16 Places (

8

 are used to connect

to MCC bus in adjacent enclosure)

MCC Right-side Bus Splice
PN-243215
6 Places

Front View