Rockwell Automation Publication 20D-RN047A-EN-P - October 2019
10
New Features and
Enhancements
This firmware revision contains the following new features and enhancements.
New Parameters Added to Define a Ground Fault Detection Fault
This firmware revision adds parameters 294 [HiHp GrdFlt Pct] and 295 [HiHp
GrdFlt Dly]. These parameters can be used to define the threshold of drive
current and delay time for a Ground Fault Detection fault to occur in frame
9…14 PowerFlex 700S with Phase II Control drives.
New Testpoint Selections
New testpoint selections 14…18 have been added to parameter 1168 [MC TP3
Select] for Rockwell Automation internal diagnostic use only.
Corrected Anomalies
There are no corrected anomalies for this firmware revision.
Known Anomalies
This firmware revision contains the following known anomalies.
294
HiHp GrdFlt Pct
Determines the threshold of percent of drive rated current for ground fault detection. This
parameter is used for frame 9…14 drives only.
Note: This parameter was added for firmware version 30.001.
Default:
Min/Max:
Units:
25.0
25.0/45.0
%
295
HiHp GrdFlt Dly
Determines the time delay for the ground fault detection. This parameter is used for frame
9…14 drives only.
Note: This parameter was added for firmware version 30.001.
Default:
Min/Max:
Units:
200.0
200.0/1500.0
mSec
1168 MC TP3 Select
Enter a value to select Motor Control (MC) data displayed in Par 1169 [MC
TP3 Value]. Par 1168 [MC TP3 Select] and Par 1169 [MC TP3 Value] are
diagnostic tools you can use to view internal drive parameters.
Note: Options 14…18 were added for firmware version 8.001 for Rockwell
Automation internal use only.
Default:
Options:
0 =
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
9 =
10 =
11 =
12 =
13 =
14 =
15 =
16 =
17 =
18 =
VdsError
VdsError
VdsRef
VdsFdbk
SlipGain
SlipGnMaxLim
SlipGnMinLim
SlipGainRtd
MaxSlipGain
MinSlipGain
KpTermSlipRg
IntgtrmSlpRg
P510Bit26
LatchedSlpGn
FltrdSlipGain
NoiseSum1
NoiseSum2
NoiseSum1max
NoiseSum2max
GFTimeAccum