Rockwell Automation Publication 520-UM002B-EN-E - December 2017
29
Installation/Wiring
Chapter 1
2.
Press and hold down the locking tab on the terminal guard.
3.
Slide the terminal guard down to remove from the Power Module.
Re-attach the terminal guard when wiring is complete.
To access the power terminals for Frame A, you need to separate the Power and
Control Modules. See
Separating the Power and Control Module on page 25
for
instructions.
Power Wiring
For general wiring and grounding practices, see Wiring and Grounding Guide,
(PWM) AC Drives, publication
.
Motor Cable Types Acceptable for 100...600 Volt Installations
A variety of cable types are acceptable for drive installations. For many
installations, unshielded cable is adequate, provided it can be separated from
sensitive circuits. As an approximate guide, allow a spacing of 0.3 m (1 ft) for
every 10 m (32.8 ft) of length. In all cases, long parallel runs must be avoided. Do
not use cable with an insulation thickness less than 15 mils (0.4 mm/0.015 in.).
Do not route more than three sets of motor leads in a single conduit to minimize
ATTENTION:
National Codes and standards (NEC, VDE, BSI, etc.) and local codes
outline provisions for safely installing electrical equipment. Installation must
comply with specifications regarding wire types, conductor sizes, branch circuit
protection and disconnect devices. Failure to do so may result in personal injury
and/or equipment damage.
ATTENTION:
To avoid a possible shock hazard caused by induced voltages,
unused wires in the conduit must be grounded at both ends. For the same
reason, if a drive sharing a conduit is being serviced or installed, all drives using
this conduit should be disabled. This will help minimize the possible shock
hazard from “cross coupled” power leads.
Summary of Contents for PowerFlex 527
Page 4: ...4 Rockwell Automation Publication520 UM002B EN E December 2017 Summary of Changes Notes...
Page 8: ...8 Rockwell Automation Publication 520 UM002B EN E December 2017 Table of Contents Notes...
Page 173: ...Rockwell Automation Publication520 UM002B EN E December 2017 173 Notes...
Page 174: ...174 Rockwell Automation Publication 520 UM002B EN E December 2017 Notes...
Page 175: ......