background image

20

Rockwell Automation Publication SAFETY-AT140A-EN-P - May 2015

Safety Function: Actuator Subsystems – Stop Category 1 via the PowerFlex 525 and PowerFlex 527 Drives with Safe Torque-off

Validation of Safe Response to Abnormal Operation - The safety system responds properly to all foreseeable faults with corresponding diagnostics.

Guardmaster Dual-input Safety Relay- Guardmaster Multifunction-delay Expansion Module Tests

Test Step

 Validation

Pass/Fail

Changes/Modifications

1

While the machine continues to run, remove the wire from L12 of the Guardmaster 
multifunction-delay expansion module. The hazardous motion must coast to a stop. 
The Logic IN and OUT status indicators of the Guardmaster multifunction-delay 
expansion module must be OFF. The Guardmaster dual-input safety relay is not 
affected.

2

Press the external Stop button. Restore the connection. The Guardmaster 
multifunction-delay expansion module Logic IN and OUT status indicators are steady 
green. Press the external Start button to resume the hazardous motion.

3

While the hazardous motion continues to run, jump 24V to the L12 terminal of the 
Guardmaster multifunction-delay expansion module. After a second or two, the 
hazardous motion coasts to a stop. The Logic IN and OUT status indicators of the 
Guardmaster multifunction-delay expansion module are OFF. The OUT status indicator 
of the Guardmaster dual-input safety relay is OFF. The PWR/Fault indicator of the 
Guardmaster dual-input safety relay blinks red to show that it is faulted. 

4

Remove the jumper. Press and release the Reset button. The Guardmaster dual-input 
safety relay must not respond.

5

Cycle power to the Guardmaster dual-input safety relay. It responds. The PWR/Fault, 
and IN1 and IN2 status indicators are steady green. The OUT status indicator blinks 
green.

6

Press and release the Reset button. Press the external Start button. The hazardous 
motion must resume.

7

While the hazardous motion continues to run, jump 0V to the L12 terminal of the 
Guardmaster multifunction-delay expansion module. After a second or two the 
hazardous motion coasts to a stop. The Logic IN and OUT status indicators of the 
Guardmaster multilfunction delay expansion module are off. The OUT status indicator 
of the Guardmaster dual-input safety relay is OFF. The PWR/Fault status indicator of 
the Guardmaster dual-input safety relay blinks red to show that it is faulted. 

8

Remove the jumper. Press and release the Reset button. The Guardmaster dual-input 
safety relay must not respond.

9

Cycle power to the Guardmaster dual-input safety relay. It responds. The PWR/Fault, 
and IN1 and IN2 status indicators are steady green. The OUT indicator blinks green.

10

Press and release the Reset button. Press the external Start button. The hazardous 
motion must resume.

Validation of Safe Response to Abnormal Operation - The safety system responds properly to all foreseeable faults with corresponding diagnostics.

 Guardmaster Multifunction-delay Expansion Module - PowerFlex Drive Tests

Test Step

Verification and Validation

Pass/Fail

Changes/Modifications

1

While the machine continues to run, remove the wire from terminal S1 of the 
PowerFlex drive. The hazardous motion must coast to a stop.The Guardmaster dual-
input safety relay and the Guardmaster multifunction-delay expansion module are 
not affected. The PowerFlex drive has an STO fault.

2

Replace the wire to terminal S1. Press the drive’s Start button. The drive must not 
respond. The STO fault remains.

3

Cycle power to the drive. The STO fault is cleared. Press the Start button. The hazardous 
motion starts.

4

While the hazardous motion continues to run, jump 24V to terminal S1 of the 
PowerFlex drive. Open the guarded gate. The hazardous motion coasts to a stop. The 
Guardmaster dual-input safety relay and the Guardmaster multifunction-delay 
expansion module behave in the normal way to the gate opening. The PowerFlex drive 
has an STO fault.

Summary of Contents for PowerFlex 525

Page 1: ... 525 Drive PowerFlex 527 Drive Safety Rating CAT 3 PLd to ISO 13849 1 2008 Topic Page Important User Information 2 General Safety Information 3 Introduction 3 Safety Function Realization Risk Assessment 3 Stop Safety Functions 4 Safety Function Requirements 4 Functional Safety Description 5 Bill of Material 6 Setup and Wiring 6 Configuration 11 Calculation of the Performance Level 13 Verification ...

Page 2: ...ent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Throughout this manual when necessary we use notes to make you aware of safety considerations Labels may also be on or inside...

Page 3: ...rd switch as in Safety Function Door Monitoring Products SensaGuard GSR DI publication SAFETY AT069 is used as a convenient example of an Input subsystem in this application technique Safety Function Realization Risk Assessment The required performance level is the result of a risk assessment and refers to the amount of the risk reduction to be carried out by the safety related parts of the contro...

Page 4: ...stem initiates and maintains a stop command for the safety system to stop hazardous motion before a person can reach the hazardous area The stop command cannot be reset until the guard door is closed Prevention of an Unexpected Startup The safety system cannot be reset and hazardous motion cannot be restarted while the guard door is open Once the guard door is closed and the stop command is reset ...

Page 5: ...ter multifunction delay expansion module is configured to provide a 100 ms delay In the event of an internal fault or a fault signaled via the SWS the Guardmaster multifunction delay expansion module immediately de energizes its safety outputs The PowerFlex drive monitor its STO inputs for valid status and faults The drive monitors its internal safety circuits for valid status and faults The drive...

Page 6: ... dual input safety relay s safety outputs energize the Guardmaster multifunction delay expansion module energizes its safety outputs and the drive s STO inputs are powered The hazardous motion can then be restarted by pressing a PAC controlled Start button PreventionofanUnexpectedStart up The Guardmaster dual input safety relay cannot be reset while its input device is in a tripped guard door open...

Page 7: ...the basis of an approach speed of the body or part of the body in our case a hand ISO 13855 defines the approach speed of a hand as 1600 mm per sec Using this value we calculate the access time 762 mm 1600 mm per sec or 476 ms ANSI B11 19 defines the approach speed of a hand as 63 in per sec Using this value we calculate the access time 30 in 63 in per sec or 476 ms OverallSystemStoppingPerformanc...

Page 8: ...function delay expansion module GSR EMD Guardmaster multifunction delay expansion module delay EMDd PowerFlex 525 drive drive overall system stopping performance less maximum safe coast to stop time 54 ms SG 35 ms GSR DI 35 ms EMD 100 ms EMDd 100 ms drive 324 ms overall system stopping performance time less the estimated maximum safe coast to stop time 476 ms 324 ms 152 ms estimated maximum safe c...

Page 9: ...y wired to the PowerFlex 525 drive This button is used for normal non safety stops and starts of the system It is also used to start restart the drive after safety related stops once the safety circuit is reset Figure 1 PowerFlex 525 Circuit 24V DC 0V DC COM Typical Safety Input Device 24V DC 0V DC Start Stop Gate control powersupply Gate control circuit Initiate Configured Normal Production Stop ...

Page 10: ...of this circuit This button is used for normal non safety stops and starts of the system It is also used to start restart the drive after safety related stops once the safety circuit is reset Figure 2 PowerFlex 527 Circuit 24V DC 0V DC COM Typical Safety Input Device 24V DC 0V DC To PAC Digital Common Gate control power supply Gate control circuit Initiate Configured Normal Production Stop Start S...

Page 11: ...mation about this relay refer to Guardmaster Safety Relay DI Installation Instructions publication 440R IN037 1 Enable Program mode 2 Set Operation mode to 2 Manual Reset IN1 and IN2 or L12 3 Cycle power to store the configuration setting Configure the Guardmaster Multifunction delay Expansion Module Follow these steps to configure the Guardmaster multifunction delay expansion module For more info...

Page 12: ... Fault status indicator will flash red 2 Set timing mode configuration Turn the Range rotary switch to 1 0 1 to 1 0 second and then turn the Time rotary switch to 1 10 The B1 and IN indicators blink the new setting The PWR Fault status indicator flashes steady green to indicate that the positions are set 3 Cycle power to the unit to store the configuration setting IMPORTANT The configuration must ...

Page 13: ...gn Environment A detailed description of how to fully configure the PowerFlex 527 drive is beyond the scope of this document For more information about this drive refer to PowerFlex 527 Adjustable Frequency AC Drive User Manual publication 520 UM002 By default the PowerFlex 527 drive provides a coast to stop in response to an STO input This action overrides any other stop type that might be config...

Page 14: ... the Rockwell Automation SISTEMA library The functional safety data for the PowerFlex 527 drive is from the PowerFlex 527 Adjustable Frequency AC Drive User Manual publication 520 UM002 Logic and Output Subsystems Calculation The PowerFlex 525 drive yields the following results This can be modeled as follows The PowerFlex 527 drive yields virtually the same results The same parts produce the same ...

Page 15: ...cal safety input device For instance when the PowerFlex 525 drive is used these are the SISTEMA calculations for the safety function Safety related stop function initiated by a safeguard When the PowerFlex 525 drive is used in the safety function Prevention of an unexpected startup the SISTEMA calculations are identical because all of the same components are used Logic Output Subsystem 1 Subsystem...

Page 16: ...ch achieve their necessary PLr When the PowerFlex 527 drive is used in the safety function Safety related stop function initiated by a safeguard the SISTEMA calculation results are as follows As before when the PowerFlex 527 drive is used in the safety function Prevention of an unexpected start up the calculations are identical because all of the same components are used Each PowerFlex 527 safety ...

Page 17: ...ocument uses as an example a SensaGuard switch for an input device Notice that in the validation process all of the purposely created faults are created at the input terminals of the Guardmaster dual input safety relay All of the relay s responses to these faults are the same as they would be using any typical input device with OSSD outputs or an electro mechanical input device using the Guardmast...

Page 18: ...us motion starts and the machine begins to operate 11 Openthe guarded door The safety system must trip The hazardous motionmust stop withintherequiredtime MonitorthestatusindicatorsontheGuardmasterdual input safety relay and Guardmaster multifunction delay expansion module for proper operation Only the PWR Fault status indicator on both devices should be steady green All other status indicators sh...

Page 19: ...rips immediately The status indicator on the SensaGuard switch blinks red The Guardmaster dual input safety relay IN1 IN2 and OUT status indicators are OFF The Guardmaster multifunction delay expansion module LoginIN and OUT status indicators are OFF 11 Remove the jumper Neither the SensaGuard switch nor the Guardmaster dual input safety relay respond Press and release the Reset button Nothing cha...

Page 20: ...xternal Start button The hazardous motion must resume 7 While the hazardous motion continues to run jump 0V to the L12 terminal of the Guardmaster multifunction delay expansion module After a second or two the hazardous motion coasts to a stop The Logic IN and OUT status indicators of the Guardmaster multilfunction delay expansion module are off The OUT status indicator of the Guardmaster dual inp...

Page 21: ... not respond The STO fault remains 10 Cyclepowertothedrive TheSTOfaultiscleared PresstheStartbutton Thehazardous motion starts 11 Repeat steps 1through 10 usingthePowerFlex drive s terminal S2inplace of terminal S1 The system responses must be the same as before Confirmation of Performance The overall systemstopping performance does not exceed 476 ms SensaGuard Switch Guardmaster Dual input Safety...

Page 22: ...uardmaster multifunction delay expansion module Guardmaster Safety Relays DI DIS SI CI GLP EM and EMD Selection Guide publication 440R SG001 Provides descriptive information about how to select and configure a Guardmaster safety relay PowerFlex 520 Series AdjustableFrequency AC Drive Quick Start Guide publication 520 QS001A Summarizes the basic steps needed to install start up and program the Powe...

Page 23: ...Rockwell Automation Publication SAFETY AT140A EN P May2015 23 Safety Function Actuator Subsystems Stop Category 1 via the PowerFlex 525 and PowerFlex 527 Drives with Safe Torque off Notes ...

Page 24: ...Documentation Feedback Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA DU002 available at http www rockwellautomation com literature Rockwell Otomasyon Ticaret A Ş Kar Plaza İş Merkezi E Blok Kat 6 34752 İçerenköy İstanbul Tel 90 216 5698400 For more information on Safety Function Capabil...

Reviews: