Using I/O Messaging
5-3
An image that uses 32-bit words for Reference and Datalinks would
change the I/O image in
as follows:
illustrates an example of an I/O image that does not use all of
the I/O data. Only the Logic Command/Reference and Datalink B are
enabled. In this example, the Reference is a 32-bit word, and Datalinks
are 16-bit words.
Figure 5.2 Example I/O Image with Only Logic/Reference and Datalink B Enabled
LSW = Least Significant Word (Bits 15 - 0)
MSW = Most Significant Word (Bits 31 - 16)
Word
I/O
Word
I/O
0
Logic Command/Status
7 - 10
Datalink B
1 - 2
Reference/Feedback
11 - 14
Datalink C
3 - 6
Datalink A
15 - 18
Datalink D
Controller
Scanner
Adapter
PowerFlex Drive
PROFIBUS
DPI
Output
Image
(Write)
Input
Image
(Read)
0 Logic Status
1 Feedback (LSW)
2 Feedback (MSW)
3 Datalink Out B1
4 Datalink Out B2
0 Logic Command
1 Reference (LSW)
2 Reference (MSW)
3 Datalink In B1
4 Datalink In B2
Logic Status
Feedback
Data Out A1
Data Out A2
Data Out B1
Data Out B2
Data Out C1
Data Out C2
Data Out D1
Data Out D2
Word and I/O
Logic Command
Reference
Data In A1
Data In A2
Data In B1
Data In B2
Data In C1
Data In C2
Data In D1
Data In D2
20COMM-UM006A-EN-P.book Page 3 Friday, September 28, 2001 10:43 AM
Summary of Contents for PowerFlex 20-COMM-P
Page 8: ...P 4 About This Manual 20COMM UM006A EN P book Page 4 Friday September 28 2001 10 43 AM...
Page 22: ...2 8 Installing the Adapter 20COMM UM006A EN P book Page 8 Friday September 28 2001 10 43 AM...
Page 30: ...3 8 Configuring the Adapter 20COMM UM006A EN P book Page 8 Friday September 28 2001 10 43 AM...
Page 94: ...7 8 Troubleshooting 20COMM UM006A EN P book Page 8 Friday September 28 2001 10 43 AM...
Page 101: ...Adapter Parameters B 5 Notes 20COMM UM006A EN P book Page 5 Friday September 28 2001 10 43 AM...
Page 102: ...B 6 Adapter Parameters 20COMM UM006A EN P book Page 6 Friday September 28 2001 10 43 AM...
Page 112: ...20COMM UM006A EN P book Page 2 Friday September 28 2001 10 43 AM...