5-6
Using I/O Messaging
These example ladder logic programs (
) work
with PowerFlex 70 or PowerFlex 700 drives.
Functions of the Example Programs
The example programs use an operator station wired to an I/O module in
Slot 0, Module Group 0, Rack 0. The operator can perform the following
actions:
•
Obtain status information from the drive.
•
Use the Logic Command to control the drive (for example, start,
stop).
•
Send a Reference to the drive.
Adapter Settings for the Example Programs
•
Node address 1 is set using the switches.
•
Logic Command/Reference and Datalink A are enabled in
Parameter 13 - [DN I/O Config]
.
•
Master-Slave Hierarchy is set using
Parameters 25 - [M-S Input]
and
26 - [M-S Output]
.
•
Polled I/O was enabled during the scanner configuration.
Scanner Settings for the Example Programs
•
The scanner is node 0 on the DeviceNet network.
•
The scanner is in slot 1.
•
The adapter I/O is mapped in word 0 and word 1.
•
Data files, when used, are pointed out in the examples.
Logic Command/Status Words
These examples use the Logic Command word and Logic Status word
for PowerFlex 70 and PowerFlex 700 drives. Refer to
to view these. The definition of the bits in
these words may vary if you are using a different DPI product. Refer to
the documentation for your drive.
Example Ladder Logic Programs
Summary of Contents for PowerFlex 20-COMM-D
Page 1: ...DeviceNet Adapter 20 COMM D FRN 1 xxx User Manual...
Page 6: ...iv Table of Contents Notes...
Page 72: ...6 14 Using Explicit Messaging Notes...
Page 90: ...B 8 Adapter Parameters Notes...
Page 122: ...C 32 DeviceNet Objects Notes...
Page 132: ...E 8 Master Slave I O Configuration Notes...
Page 148: ......