RSNetWorx Configuration for PLC-5C Applications
4-13
Figure 4.19 Integer Files for ControlNet Communications Screen
9.
Enter the input and output size for the node on the network. The
number of words selected depends on the I/O to be communicated
with the node. In this example, the Node 2 PowerFlex 70 is set for all
I/O enabled which equates to 10 words of I/O (
Figure 4.20 Input / Output Table
Important:
The size of the Reference (
Parameter 7- [Ref/Fdbk Size]
)
and Datalinks (
Parameter 8- [Datalink Size]
) will affect
the size you configure for the network I/O. For example,
32-bit Datalinks requires twice as many words as 16-bit
Datalinks. Depending on your application, the configured I/
O size may vary.
Note the values in the Input Address and Output Address fields. These
are needed to develop a ladder program.
Words
Input to PLC-5C
Output to PLC-5C
0-1
Logic Command / Reference
Logic Status / Feedback
2-3
Datalinks A1 & A2 Out
Datalinks A1 & A2 In
4-5
Datalinks B1 & B2 Out
Datalinks B1 & B2 In
6-7
Datalinks C1 & C2 Out
Datalinks C1 & C2 In
8-9
Datalinks D1 & D2 Out
Datalinks D1 & D2 In
20COMM-UM003A-EN-P.book Page 13 Wednesday, November 7, 2001 3:46 PM
Summary of Contents for PowerFlex 20-comm-c FRN 1. Series
Page 6: ...iv Table of Contents Notes 20COMM UM003A EN P book Page iv Wednesday November 7 2001 3 46 PM...
Page 18: ...1 8 Getting Started 20COMM UM003A EN P book Page 8 Wednesday November 7 2001 3 46 PM...
Page 114: ...B 6 Adapter Parameters Notes 20COMM UM003A EN P book Page 6 Wednesday November 7 2001 3 46 PM...
Page 152: ...Glossary 6 Notes 20COMM UM003A EN P book Page 6 Wednesday November 7 2001 3 46 PM...
Page 154: ...20COMM UM003A EN P book Page 2 Wednesday November 7 2001 3 46 PM...