Rockwell Automation Publication 750-IN001O-EN-P - October 2014
103
Lift and Mount the Drive
Chapter 3
Figure 64 - IP20, NEMA/UL Type 1, MCC Style Cabinet, Floor Mount Frame 9
Enclosure Code L, P, W - 800 mm Deep Drive with Cabinet Options Bay.
M12 (1/2 in.) Property Class 8.8 anchoring hardware recommended to
fasten the drive cabinet through its internal mounting angle to the
foundation. Anchor bolts may be pre-located and embedded in the
foundation prior to instillation.
1800
(70.9)
440
(17.3)
440
(17.3)
2453
(96.6)
2300
(90.6)
800
(31.5)
240
(9.4)
➊
➊
440
(17.3)
➊
➐
270
(10.6)
270
(10.6)
1464
(57.6)
➌
➍
➏
➋
127
(5.0)
➋
127
(5.0)
76
(3.0)
➎
No.
Description
➊
Power wiring conduit plates.
➋
Control wiring conduit plates.
➌
Optional exhaust hood.
➍
Optional HIM.
➎
Option bay disconnect switch access door.
➏
Interlock override switch.
For instructions and precautions refer to the
Hardware Service Manual,
➐
Recommended seven-hole anchoring.
BOTTOM
TOP
Summary of Contents for PowerFlex 20-750-20COMM
Page 1: ...PowerFlex 750 Series AC Drives Catalog Numbers 20F 20G 21G Installation Instructions...
Page 6: ...6 Rockwell Automation Publication 750 IN001O EN P October 2014 Notes...
Page 10: ...10 Rockwell Automation Publication 750 IN001O EN P October 2014 Preface Notes...
Page 218: ...218 Rockwell Automation Publication 750 IN001O EN P October 2014 Chapter 4 Power Wiring Notes...