Publication 2711P-UM001A-EN-P
Installing and Replacing Components
5-15
For PanelView Plus 1250 (has 2 Backlights)
Work on a clean, flat, stable surface to protect the display from
debris, scratches and damage.
8.
Remove the 2 screws that secure each of the two backlights and
then remove the backlights.
9.
Insert the new backlights and then secure each with the 2
screws.
10.
Attach the Backlight Connector to the circuit board (shown in
step 5 on page 5-14).
11.
Attach the LCD Display Connector to the circuit board (shown in
step 4 on page 5-13).
12.
Secure the LCD Display by attaching the 4 screws. The terminals
use different size screws. Use the following chart to tighten the
screws.
13.
Replace the Display Module bezel as described on 5-12.
Backlights
PanelView Plus
Screw Size Torque
700
2.5 mm
.68 N•m (6-8 in-lb)
1000/1250
#4
.68 N•m (6-8 in-lb)
1500
#6
.90 - 1.1 N•m (8-10 in-lb)