72
Rockwell Automation Publication 2711R-UM001E-EN-E - January 2017
Chapter 4
Cable Connections and Communication
Ethernet Connection
The PanelView 800 terminals have an Ethernet port that supports:
• communication to a controller.
• connection to a computer for accessing the PanelView Explorer Startup
window and downloading applications from Connected Components
Workbench to the terminal.
Ethernet Connector
The base-configured unit of the terminals has an RJ45, 10/100 Base-T connector
for Ethernet network communication.
Ethernet Connector Pinout
Either a standard Ethernet cable or crossover cables such as 2711P-CBL-EX04
can be used when connecting directly to a logic controller or switch.
Cables
The PanelView 800 terminals require category 5 twisted-pair cables. The
maximum cable length between the terminal’s Ethernet port and a 10/100
Base-T port on an Ethernet hub (without repeaters or fiber) is 100 m (328 ft). In
industrial applications, keep the cable length to a minimum.
For additional information, refer to the Ethernet Design Considerations
reference manual, publication
Pin
Pin
Pin Name
Looking into RJ45
Connector
1
TD+
2
TD-
3
RD+
4
NC
5
NC
6
RD-
7
NC
8
NC
Shield Connection
Chassis Gnd
Ethernet port
2711R-T4T
2711R-T7T
2711R-T10T
1
8
Summary of Contents for PanelView 800 2711R-T10T
Page 1: ...User Manual PanelView 800 HMI Terminals Catalog Numbers 2711R T4T 2711R T7T 2711R T10T...
Page 4: ...4 Rockwell Automation Publication 2711R UM001E EN E January 2017 Summary of Changes Notes...
Page 8: ...8 Rockwell Automation Publication 2711R UM001E EN E January 2017 Table of Contents Notes...
Page 98: ...98 Rockwell Automation Publication 2711R UM001E EN E January 2017 Chapter 7 Recipes Notes...
Page 156: ...156 Rockwell Automation Publication 2711R UM001E EN E January 2017 Index Notes...
Page 157: ......