Publication 1764-UM001A-US-P
Wiring Your Controller
3-5
As shown in the illustration below, these surge suppression circuits connect directly
across the load device.
Recommended Surge Suppressors
Use the Allen-Bradley surge suppressors shown in the following table for use with
relays, contactors, and starters.
Suppressor Device
Coil Voltage
Catalog Number
Bulletin 509 Motor Starter
Bulletin 509 Motor Starter
120V ac
240V ac
599-K04
599-KA04
Bulletin 100 Contactor
Bulletin 100 Contactor
120V ac
240V ac
199-FSMA1
199-FSMA2
Bulletin 709 Motor Starter
120V ac
1401-N10
Bulletin 700 Type R, RM Relays
ac coil
None Required
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
12V dc
12V dc
700-N22
700-N28
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
24V dc
24V dc
700-N10
700-N13
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
48V dc
48V dc
700-N16
700-N17
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
115-125V dc
115-125V dc
700-N11
700-N14
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
230-250V dc
230-250V dc
700-N12
700-N15
Bulletin 700 Type N, P, or PK Relay
150V max, ac or DC
700-N24
Miscellaneous electromagnetic
devices limited to 35 sealed VA
150V max, ac or DC
700-N24
Surge Suppression for Inductive dc Load Devices
Output Device
Diode
_
+
(A surge suppressor can also be used.)
Summary of Contents for micrologix 1500
Page 1: ...MicroLogix 1500 Programmable Controllers Bulletin 1764 User Manual AB Spares...
Page 6: ...Publication 1762 RM001A US P Preface P 4...
Page 52: ...Publication 1764 UM001A US P 3 16 Wiring Your Controller...
Page 78: ...Publication 1764 UM001A US P 5 10 Using Trim Pots and the Data Access Tool DAT...
Page 96: ...Publication 1764 UM001A US P B 6 Replacement Parts...
Page 102: ...Publication 1764 UM001A US P C 6 Troubleshooting Your System...
Page 132: ...Publication 1764 UM001A US P F 10 System Loading and Heat Dissipation...
Page 147: ...AB Spares...
Page 149: ...AB Spares...