Publication 1762-UM002A-EN-P - July 2002
3-6
Module Data, Status, and Channel Configuration
Enabling or Disabling a Channel (Bit 15)
You can enable or disable each of the four channels individually using
bit 15. The module only scans enabled channels. Enabling a channel
forces it to be recalibrated before it measures input data. Disabling a
channel sets the channel data word to zero.
Selecting Data Formats (Bits 14 through 12)
This selection configures channels 0 through 3 to present analog data
in any of the following formats:
•
Raw/Proportional Data
•
Engineering Units x 1
•
Engineering Units x 10
•
Scaled for PID
•
Percent Range
TIP
When a channel is not enabled (0), no input is
provided to the controller by the A/D converter.
This speeds up the response of the active channels,
improving performance.
Table 3.1 Channel Data Word Format
Input
Type
Data Format
Engineering Units x1
Engineering Units x10
Scaled-for-PID
Raw/Proportion
al Data
Percent
Range
°C
°F
°C
°F
J
-2100 to +12000
-3460 to +21920
-210 to +1200
-346 to +2192
0 to +16383
-32767 to +32767
0 to +10000
K
-2700 to +13700
-4540 to +24980
-270 to +1370
-454 to +2498
0 to +16383
-32767 to +32767
0 to +10000
T
-2700 to +4000
-4540 to +7520
-270 to +400
-454 to +752
0 to +16383
-32767 to +32767
0 to +10000
E
-2700 to +10000
-4540 to +18320
-270 to +1000
-454 to +1832
0 to +16383
-32767 to +32767
0 to +10000
R
0 to +17680
+320 to 32140
0 to +1768
+32 to 3214
0 to +16383
-32767 to +32767
0 to +10000
S
0 to +17680
+320 to 32140
0 to +1768
+32 to 3214
0 to +16383
-32767 to +32767
0 to +10000
B
+3000 to 18200
+5720 to 32767
(1)
+300 to 1820
+572 to 3308
0 to +16383
-32767 to +32767
0 to +10000
N
-2100 to +13000
-3460 to +23720
-210 to +1300 -346 to +2372
0 to +16383
-32767 to +32767
0 to +10000
C
0 to +23150
+320 to 32767
0 to +2315
+32 to 4199
0 to +16383
-32767 to +32767
0 to +10000
±50 mV
-5000 to +5000
-500 to +500
(2)
0 to +16383
-32767 to +32767
0 to +10000
±100 mV -10000 to 10000
-1000 to 1000
0 to +16383
-32767 to +32767
0 to +10000
(1) Type B and C thermocouples cannot be represented in engineering units x1 (°F) above 3276.7 °F; therefore, it will be treated as an over-range error.
(2) When millivolts are selected, the temperature setting is ignored. Analog input date is the same for °C or °F selection.
Summary of Contents for MicroLogix 1200
Page 1: ...MicroLogix 1200 Thermocouple mV Input Module Catalog Number 1762 IT4 User Manual AB Parts...
Page 10: ...Publication 1762 UM002A EN P July 2002 Preface 4...
Page 68: ...Publication 1762 UM002A EN P July 2002 3 38 Module Data Status and Channel Configuration...
Page 76: ...Publication 1762 UM002A EN P July 2002 4 8 Diagnostics and Troubleshooting...
Page 143: ...AB Parts...