Connect the Kinetix 5700 Drive System
Chapter 5
Ungrounded Power Configurations
The ungrounded power configuration (
), corner-grounded
), and impedance-grounded (
) power configurations do
not provide a neutral ground point.
Figure 59 - Ungrounded Power Configuration
Refer to
beginning on
for input power
interconnect diagrams.
IMPORTANT
If you determine that you have ungrounded, corner-grounded, or
impedance-grounded power distribution in your facility, you must remove
the ground screws in each of your DC-bus power supplies and iTRAK power
supplies and install the ground screw/jumper in each of your dual-axis and
single-axis inverters.
Refer to
L3
L2
L1
L3 L2 L1
Transformer
Three-phase
Input VAC
Chassis Ground
Bonded Cabinet
Ground
Ground Grid or
Power Distribution Ground
Connect to drive module
ground stud.
Three-phase
AC Line Filter
Circuit
Protection
2198-P
xxx
DC-bus Power Supply
(bottom view)
M1
Contactor
ATTENTION:
Ungrounded systems do not reference each phase potential to
a power distribution ground. This can result in an unknown potential to earth
ground.