2
Rockwell Automation Publication 2198-IN017A-EN-P - July 2019
Kinetix 5100 AC Line Filter
Install the AC Line Filter
Mount the line filter to the cabinet panel with hardware as specified in this table.
See the System Design for Control of Electrical Noise Reference Manual, publication
for techniques on how to make proper high-frequency (HF) bonds to improve
overall system performance.
Wire the AC Line Filter
Wire by using copper with 75 °C (167 °F) minimum rating. The phase of main AC power is
arbitrary and earth ground connection is required for safe and proper operation.
Cat. No.
Mounting Bolts
Torque Value
N•m (lb•in)
2198-DB111-F
M5 (#10-24)
1.6…2.0 (13.9…17.70)
2198-DB127-F
2198-DB310-F
2198-DB324-F
2198-DB335-F
2198-DB356-F
IMPORTANT
The National Electrical Code and local electrical codes take precedence over the values and
methods provided.