Rockwell Automation Publication 2097-UM002D-EN-P - April 2017
75
Connect the Kinetix 350 Drive System
Chapter 4
to locate the connector on your Logix5000™ communication
module.
Shielded Ethernet cable is available in lengths up to 78 m (256 ft). However,
the total length of Ethernet cable connecting drive-to-drive, drive-to-
controller, or drive-to-switch must not exceed 100 m (328 ft).
If the entire channel is constructed of stranded cable (no fixed cable), then this
equation is for calculating maximum length:
Maximum Length = (113-2N)/y, meters
where N = the number of connections in the channel
and y = the loss factor that is compared to fixed cable (typically 1.2…1.5).
Figure 44 - CompactLogix Ethernet Port Location
The Port 1 Ethernet connection is used for connecting to a Logix5000™
controller and to configure your Kinetix 350 drive.
Figure 45 - Ethernet Wiring Example - External Switch
Ethernet Cable Connections on page 74
for information on how to use an unmanaged switch in your application.
The Ethernet ports are on
bottom of controller.
CompactLogix™ Controller Platform
1769-L33ERM Shown
2
3
5
4
1
R
W
P
CompactLogix Controller Platform
1769-L33ERM Shown
Personal Computer
1783-US05T
Stratix 2000
Switch
(1)
Kinetix 350 Drives