Rockwell Automation Publication 450L-IN009A-EN-P - March 2022
GuardShield 450L PAC Safety Light Curtain Installation Instructions
Figure 9 - Use the Integrated Laser Alignment System for Positioning
The450L PAC is a Perimeter Access Control safety light curtain that is designed for
whole body detection to create a safety perimeter around a machine or hazardous
location. To verify correct operation, first place the machine or hazardous location
in a safe state. Then interrupt the beams, refer to
for the beam positions
of different models. Confirm that the OSSD safety output switches to the OFF state
(refer to
for the indicator status) and remains OFF for as long as
the beams are interrupted.
Figure 10 - 450L PAC Overall and Mounting Dimensions
Figure 11 - 450L PAC Beam Heights
ATTENTION:
Do not stare into the beam. Laser Class 2.
Conforms to 21 CFR 1040.10.
Laser
Optical Switch
30 mm
(1.18 in.)
30 mm
(1.18 in.)
30 mm
(1.18 in.)
30 mm
(1.18 in.)
42.5 mm
(1.67 in.)
13 mm
(0.51 in.)
29.9 mm
(1.18 in.)
8 mm
(0.31 in.)
17.6 mm
(0.69 in.)
14.9 mm
(0.59 in.)
7.6 mm
(0.3 in.)
A
B
C
D
Cat. No.
Number of
Beams
A
B
C
D
Protective
Height
Mounting
Value
Mounting
Value
Total Length
450L-
E4A1L0150YD
1
150 mm
(5.91 in.)
185.5 mm
(7.3 in.)
215 mm
(8.46 in.)
235 mm
(9.25 in.)
450L-
E4A2L0600YD
2
600 mm
(23.62 in.)
635.5 mm
(25.02 in.)
665 mm
(26.18 in.)
685 mm
(26.97 in.)
450L-
E4A3L0900YD
3
900 mm
(35.43 in.)
935.5 mm
(36.83 in.)
965 mm
(37.99 in.)
985 mm
(38.78 in.)
450L-
E4A4L1050YD
4
1050 mm
(41.34 in.)
1085.5 mm
(42.74 in.)
1115 mm
(43.9 in.)
1135 mm
(44.68 in.)
Table 1 - DIP Switch Functionality
450L-APR-ON-5:
450L-APR-EDM-8:
DIP 1…4
DIP 1…8
50L-APU-UN-8:
450L-APR-MU-8:
DIP 1…12
DIP 1…12
Switch Number
Switch Function
Default
Description
1
—
OFF
—
2
Low range activation
OFF
OFF: Disabled
ON: Enabled
3
Beam coding
OFF
OFF: Disabled
ON: Enabled
4
—
OFF
OFF: Disabled
ON: Invalid selection
(error)
5
Combination activation of
the following start modes:
Automatic start
Manual (re) start
Manual cold start
Manual start with off
function
OFF
DIP 5: OFF
DIP 6: OFF
Automatic start (Default)
DIP 5: ON
DIP 6: OFF
Manual (re) start
DIP 5: OFF
DIP 6: ON
Manual cold start
DIP 5: ON
DIP 6: ON
Manual start with off
function
6
OFF
7
External Device Monitor
OFF
—
8
Muting
OFF
For details, see
publication
in
9
OFF
10
OFF
11
OFF
12
—
OFF
—
Distance
to r
eference plan
e (for
exam
ple
, ground)