Allen-Bradley GuardShield 450L PAC Installation Instructions Download Page 2

2

Rockwell Automation Publication 450L-IN009A-EN-P - March 2022

GuardShield 450L PAC Safety Light Curtain Installation Instructions

Figure 9 - Use the Integrated Laser Alignment System for Positioning

The450L PAC is a Perimeter Access Control safety light curtain that is designed for 
whole body detection to create a safety perimeter around a machine or hazardous 
location. To verify correct operation, first place the machine or hazardous location 
in a safe state. Then interrupt the beams, refer to 

Figure 11

 for the beam positions 

of different models. Confirm that the OSSD safety output switches to the OFF state 
(refer to 

Table 2 on page 3

 for the indicator status) and remains OFF for as long as 

the beams are interrupted.

Figure 10 - 450L PAC Overall and Mounting Dimensions

Figure 11 - 450L PAC Beam Heights

ATTENTION: 

Do not stare into the beam. Laser Class 2. 

Conforms to 21 CFR 1040.10.

Laser

Optical Switch

30 mm 

(1.18 in.)

30 mm 

(1.18 in.)

30 mm 

(1.18 in.)

30 mm 

(1.18 in.)

42.5 mm 

(1.67 in.)

13 mm 

(0.51 in.)

29.9 mm 

(1.18 in.)

8 mm 

(0.31 in.)

17.6 mm 

(0.69 in.)

14.9 mm 

(0.59 in.)

7.6 mm 

(0.3 in.)

A

B

C

D

Cat. No.

Number of 

Beams

A

B

C

D

Protective 

Height

Mounting 

Value

Mounting 

Value

Total Length

450L-

E4A1L0150YD

1

150 mm
(5.91 in.)

185.5 mm

(7.3 in.)

215 mm

(8.46 in.)

235 mm

(9.25 in.)

450L-

E4A2L0600YD

2

600 mm 

(23.62 in.)

635.5 mm 
(25.02 in.)

665 mm 

(26.18 in.)

685 mm 

(26.97 in.)

450L-

E4A3L0900YD

3

900 mm 

(35.43 in.)

935.5 mm 
(36.83 in.)

965 mm 

(37.99 in.)

985 mm 

(38.78 in.)

450L-

E4A4L1050YD

4

1050 mm 
(41.34 in.)

1085.5 mm 

(42.74 in.)

1115 mm

(43.9 in.)

1135 mm 

(44.68 in.)

Table 1 - DIP Switch Functionality

450L-APR-ON-5:
450L-APR-EDM-8:

DIP 1…4
DIP 1…8

50L-APU-UN-8:
450L-APR-MU-8:

DIP 1…12
DIP 1…12

Switch Number

Switch Function

Default

Description

1

OFF

2

Low range activation

OFF

OFF: Disabled

ON: Enabled

3

Beam  coding

OFF

OFF: Disabled

ON: Enabled

4

OFF

OFF: Disabled

ON: Invalid selection 

(error)

5

Combination activation of 

the following start modes:

Automatic start

Manual (re) start

Manual cold start

Manual start with off 

function

OFF

DIP 5: OFF
DIP 6: OFF

Automatic start (Default)

DIP 5: ON

DIP 6: OFF

Manual (re) start

DIP 5: OFF

DIP 6: ON

Manual cold start

DIP 5: ON
DIP 6: ON

Manual start with off 

function

6

OFF

7

External Device Monitor

OFF

8

Muting

OFF

For details, see 

publicatio

450L-UM001

 

in 

Additional Resource 

on page 4

9

OFF

10

OFF

11

OFF

12

OFF

Distance 

to r

eference plan

e (for 

exam

ple

, ground)