Troubleshooting
Chapter 11
View the PWR/Fault Status
Indicator (Step 1)
The first troubleshooting step is to examine the PWR/Fault status indicator on
the front of your GSR module. See
for status indicator location.
Figure 57 - PWR/Fault Status Indicator
The PWR/Fault status indicator has five possible states:
TIP
The PWR/Fault status indicator is located in the same position on all
GSR modules.
Status
Description
Action
Off
No power to the relay.
Apply power.
Solid green
The relay is in the run state.
None.
Solid red
The relay is in a non-recoverable
faulted state.
See
.
Flashing red
A non-recoverable faulted state
See
.
Green and flashing red
A recoverable faulted state.
.
IMPORTANT
For accurate diagnostics, always start counting the flashing after the first
pause. The first cycle can be inaccurate.
PWR/Fault status indicator
Table 10 - PWR/Fault Status Indicator Is Solid Red
Indicator
Description
Model
Possible Causes
Corrective Action
Solid red
Faults that are not
described in
and
result in a
solid red indicator.
All
• A momentary power interruption.
• Noise on the power or signal wires.
• Cycle power to clear the fault and return the GSR safety
relay to an operational state.
• Reconfigure the safety relay (see
• See additional information in
.
CI, DI, DIS, and SI
Short circuit has occurred, or is present, from
+24V DC (A1) to S11 or S21 or from 24V Common
(A2) to S11 or S21.
DIS
Short circuit has occurred, or is present, from
+24V DC (A1) to 14 or 24.
SI
Excessive capacitance from input wiring to
ground, but not enough to cause flashing red four
times.