58
Rockwell Automation Publication 440R-UM013E-EN-P - March 2017
Chapter 9
Application and Wiring Examples
The EMD safety relay in
is configured for a maximum of a
100-second jog. The single wire safety signal from terminals L11 to L12
enables the EMD safety relay. When enabled, the jog switch can be pressed and
held closed to turn on the EMD safety relay outputs. If the jog button is
released before the 100 second time, the EMD safety relay outputs turn off. If
the jog button is held longer than 100 seconds, the EMD safety relay outputs
only turn on for 100 seconds.
Figure 51 - EMD - Jog
SI Safety Relay
(Cat
. N
o
. 440R
-S12R2)
The SI safety relay monitors a gate interlock with mechanical contacts in
. The SI safety relay is configured for automatic reset. When the gate
is closed, the SI safety relay outputs turn on if contactors K1 and K2 are already
off. The Start button can then be pressed to turn on contactors K1 and K2.
Figure 52 - SI Example
A1
L11
X32
B1 B2
L12
18
38 48
28
17
37
47
27
A2
EMD
440R-EM4R2D
RANGE
TIME
0
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
10
9
S11
S12
S21
S22
S34 A1 13
L11 A2
14
23
24
Y32
SI
440R-S12R2
RESET
0
MM
AM
K1
24V DC
24V Com
K2
K6
K5
K3
K4
Reset
Jog
To PLC
K1
K2
K3 K4 K5
K6
K1
24V DC
24V Com
K2
Start
Stop
To PLC
K1
K2
S11
S12
S21
S22
S34
A1
13
L11 A2
14
23
24
Y32
SI
440R-S12R2
RESET
0
MM
AM