130
Rockwell Automation Publication 1756-UM022D-EN-P - May 2017
Chapter 7
Go Online with the Controller
5. Follow the directions in this table to complete the download based on
the Logix Designer application’s response.
Following a successful download, the safety-locked status and safety task
signature of the controller match the project that was downloaded. Safety data
is initialized to the values that existed when the safety task signature was
created.
Upload
Follow these steps to transfer a project from the controller to your computer.
1. Define the path to the controller.
a. Click Who Active
.
b. Select the controller.
To expand a level, click the + sign. If a controller is already selected,
make sure that it is the correct controller.
2. Click Upload.
If the software indicates
Then
Download to the controller.
Choose Download.
The project downloads to the controller and goes online.
Unable to download to the controller. Mismatch between the offline project
and the controller serial number. Selected controller may be the wrong
controller.
Connect to the correct controller or verify that this is the correct controller. If it is the correct
controller, check the Update project serial number checkbox to allow the download to proceed.
The project serial number is modified to match the controller serial number.
Unable to download to the controller. The major revision of the offline project
and the controller’s firmware are not compatible.
Choose Update Firmware.
(1)
Choose the required revision and click Update. Click Yes to confirm
your selection.
Unable to download to controller. The safety partner is missing or unavailable.
Cancel the download process. Install a compatible safety partner before attempting to
download.
Unable to download to controller. The firmware revision of the safety partner is
not compatible with the primary controller.
Update the firmware revision of the safety partner. Choose Update Firmware.
required revision and click Update. Click Yes to confirm your selection.
Unable to download to controller. Safety partnership has not been established. Cancel this download process and attempt a new download.
Unable to download to controller. Incompatible safety task signature cannot be
deleted while the project is safety-locked.
Cancel the download. To download the project, you must safety-unlock the offline project,
delete the safety task signature, and download the project.
IMPORTANT:
The safety system requires revalidation.
Cannot download in a manner that preserves the safety task signature.
Controller’s firmware minor revision is not compatible with safety task
signature in offline project.
• If the firmware minor revision is incompatible, to preserve the safety task signature, update
the firmware revision in the controller to exactly match the offline project. Then download
the offline project.
• To proceed with the download despite the safety task signature incompatibility, click
Download. The safety task signature is deleted.
IMPORTANT:
The safety system requires revalidation.
Unable to download to controller. Controller is locked. Controller and offline
project safety task signatures do not match.
Choose Unlock. The Safety Unlock for Download dialog box appears. If the Delete Signature
checkbox is selected and you choose Unlock, click Yes to confirm the deletion.
A nonrecoverable safety fault will occur in the safety controller. No designated
coordinated system time (CST) master exists.
Check Enable Time Synchronization and click Download to proceed.
(1) The controller must be unlocked.
Controller
Project
Upload
Summary of Contents for GuardLogix 5570
Page 8: ...8 Rockwell Automation Publication 1756 UM022D EN P May 2017 Table of Contents...
Page 20: ...20 Rockwell Automation Publication 1756 UM022D EN P May 2017 Chapter 1 System Overview Notes...
Page 169: ...Rockwell Automation Publication 1756 UM022D EN P May 2017 169 Index Notes...
Page 170: ...170 Rockwell Automation Publication 1756 UM022D EN P May 2017 Index Notes...
Page 171: ......