FlexLogix Controller System
13
Publication 1794-IN002F-EN-P - October 2002
4.
Make sure power is not applied to the power supply. Connect the
power supply to the adapter. This diagram and its related instructions
describe a 1794-PS13 power supply.
a. C24V dc input to the left adapter connector, terminal
A
, to the
bottom, left power connector, terminal
G
.
b. Connect -24V common to left adapter connector, terminal
B
, to the top,
left power connector, terminal
E
.
c. Use connections
C
and
D
on the adapter and connection
F
and
H
on the
power supply to pass 24V dc power and common to the next module in
the series, if required.
Use the screw-terminal connector plug that comes with the adapter to meet
the requirements for installations in Class I, Division 2 locations.
5.
Connect I/O terminal bases and I/O modules to the adapter the same way
you connect them to the controller.
6.
Remove the plastic spacer from both ends of the extended-local I/O cable
(1794-CE1 or 1794-CE3).