background image

     

5

Publication 1794-IN129B-EN-P - April 2009

 

General (Output)

Attribute

Value

Number of outputs

4 isolated (1794-OF4IXT)

 

2 isolated (1794-IF2XOF2XT)

Resolution

 

Voltage

 

Current

15 bits plus sign

 

0.320 mV/cnt 

 

0.656 

μ

A

/

cnt 

Update rate

2.5/5.0/7.5 ms all channels (see input update rate table)

 

2.5/5.0 ms all channels (see input update rate table) (1794-OF4IXT)

Output current terminal 

0 mA output until module is configured

 

4…20 mA (user configurable

 

0…20 mA (user configurable

Output voltage terminal 

0V output until module is configured

 

±10V user configurable)

 

0…10V user configurable)

 

±5V user configurable)

 

0…5V user configurable)

Current load on voltage 
output

3 mA maximum

Resistive load on current 
output

0…750 

Ω

General 

Attribute

Value

Module location

Cat. No. 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3T, 1794-TB3TS, 
and 1794-TBN

Data format

2’s complement

 

2’s complement %

 

binary

 

offset binary

Conversion type

Sigma Delta 

 

Digital to analog converter (1794-OF4IXT)

Update rate

2.5/5.0/7.5 ms all channels (see input update rate table)

 

2.5/5.0 ms all channels (see input update rate table) (1794-OF4IXT)

Normal mode rejection ratio 
- voltage or current Terminal

-3 dB @ 12 Hz (300 Hz conversion rate)

 

-80 dB @ 50 Hz (300 Hz conversion rate)

 

-3 dB @ 6 Hz (150 Hz conversion rate)

 

-80 dB @ 60 Hz (150 Hz conversion rate)

Common mode rejection 
ratio

-120 dB @ 50/60 Hz

Step response to 63% - 
voltage or current terminal 
(1794-IF4IXT, 
1794-IF2XOF2XT)

1200 Hz conversion rate = 0.6 ms

 

600 Hz conversion rate = 06.7 ms

 

300 Hz conversion rate = 13.4 ms

 

150 Hz conversion rate = 26.7 ms

Step response to 63% of full 
scale (1794-OF4IXT, 
1794-IF2XOF2XT)

< 25 

μ

s

Absolute accuracy

(1)

 

voltage terminal

 

current terminal

 

0.1% Full Scale @ 25 °C

 

0.1% Full Scale @ 25 °C

Accuracy drift with 
temperature

 

Voltage terminal

 

 

Current terminal

 

 

0.0028% Full Scale/°C (1794-IF4IXT, 1794-IF2XOF2XT)

 

0.0012% Full Scale/°C (1794-OF4IXT)

 

0.0038% Full Scale/°C (1794-IF4IXT, 1794-IF2XOF2XT)

 

0.0025% Full Scale/°C (1794-OF4IXT)

Calibration required

Factory calibrated. Can be calibrated in field when necessary

Maximum overload

30V continuous or 32 mA continuous, one channel at a time.

Indicators

1 red/green power/status indicator

Isolation voltage

120V (continuous), Basic Insulation Type, when used with 1794-TB2, 
1794-TB3, 1794-TB3S, 1794-TB3T, or 1794-TB3TS

 

250V (continuous), Basic Insulation Type, when used with 1794-TBN

 

Type tested at 1500V AC for 60 s and Routine tested at 2550V DC for 
1 s, between channel to power, channel to system, and power to 
system, and channel to channel

Flexbus current

50 mA

Power dissipation

2.0 W maximum @ 31.2V DC

Thermal dissipation

Maximum 6.8 BTU/hr @ 31.2V DC

Keyswitch position

3 (1794-IF4IXT)

 

4 (1794-OF4IXT)

 

5 (1794-IF2XOF2XT)

External DC Power Supply 
voltage

 

Voltage range

 

Supply current

 

 

24V DC nominal

 

19.2…31.2V DC (includes 5% AC ripple)

 

80 mA @ 24V DC (1794-IF4IXT)

 

210 mA @ 24V DC (1794-OF4IXT)

 

150 mA @ 24V DC (1794-IF2XOF2XT)

Dimensions 

46 mm x 94 mm x 75 mm (1.8 in. x 3.7 in. x 2.95 in.)  with module 
installed in base 

Wire size

Determined by installed terminal base

Wiring category

(2)

2 - on signal ports
2 - on power ports

Wire type

Shielded on signal ports

Enclosure

None (open-style)

Terminal screw torque

Determined by installed terminal base

North American temp code

T4

IEC temp code

T4

(1)

Includes offset, gain, nonlinearity and repeatability error terms.

(2)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and 
Grounding Guidelines, publication 

1770-4.1.

Environmental

Attribute

Value

Operating 
temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

 

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

 

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

 

-20…70 °C (-4…158 °F)

Non-operating 
temperature

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),

 

IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),

 

IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):

 

-40…85 °C (-40…185 °F)

Relative 
humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

 

5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

 

5 g @ 10…500 Hz

Operating shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

 

30 g

Non-operating 
shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

 

50 g

Emissions

CISPR 11:

 

Group 1, Class A (with appropriate enclosure)

ESD immunity

IEC 61000-4-2:

 

6 kV contact discharges

 

8 kV air discharges

General 

Attribute

Value

Summary of Contents for FLEX XT I/O 1794-IF2XOF2IXT

Page 1: ...n addition to this publication see Industrial Automation Wiring and Grounding Guidelines for additional installation requirements Allen Bradley publication 1770 4 1 NEMA Standards 250 and IEC 60529 as applicable for explanations of the degrees of protection provided by different types of enclosure WARNING If you insert or remove the module while backplane power is on an electrical arc can occur Th...

Page 2: ...erall temperature code of the system Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation Les produits marqués CL I DIV 2 GP A B C D ne conviennent qu à une utilisation en environnements de Classe I Division 2 Groupes A B C D dangereux et non dangereux Chaque produit est livré avec des marquages sur sa plaque d...

Page 3: ...Current Transmitter Current Input DC only Current Input 2 Wire Current Transmitter Current only Current Input 3 Wire Transmitter DC only Voltage Input I I 51 33 1794 TBN shown 3 Wire Transmitter Word 2 Read Back Channel 2 Word 3 Read Back Channel 3 Word 4 PU FP CF 0 Reserved 0 0 0 0 0 BD DN 0 Word 5 0 0 0 0 P3 P2 P1 P0 0 0 0 0 W3 W2 W1 W0 1794 IF2XOF2XT Word 0 Analog value for Input channel 0 Word...

Page 4: ...5 ms 5 0 ms 0 1 1 0 0 10V 5 0 ms 5 0 ms 0 1 1 1 10V 5 0 ms 5 0 ms 1 0 0 0 0 20 mA 2 5 ms 2 5 ms 1 0 0 1 4 20 mA 7 5 ms 5 0 ms 1 0 1 0 0 10V 2 5 ms 2 5 ms 1 0 1 1 0 5V 2 5 ms 2 5 ms 1 1 0 0 20 mA 2 5 ms 2 5 ms 1 1 0 1 4 20 mA 7 5 ms 5 0 ms 1 1 1 0 10V 2 5 ms 2 5 ms 1 1 1 1 5V 2 5 ms 2 5 ms Configuration Bits MSD LSD Nominal Range Data Type Output Values ModuleUpdate Rate 0 0 0 1 4 20 mA Signed 2 s ...

Page 5: ...or 32 mA continuous one channel at a time Indicators 1 red green power status indicator Isolation voltage 120V continuous Basic Insulation Type when used with 1794 TB2 1794 TB3 1794 TB3S 1794 TB3T or 1794 TB3TS 250V continuous Basic Insulation Type when used with 1794 TBN Type tested at 1500V AC for 60 s and Routine tested at 2550V DC for 1 s between channel to power channel to system and power to...

Page 6: ... at http www ab com for Declaration of Conformity Certificates and other certification details Attribute Value c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File E65584 UL Listed for Class I Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Cont...

Reviews: