Publication 1794-IN129B-EN-P - April 2009

Installation Instructions

FLEX XT I/O Isolated Input Analog Module 

Cat. No. 1794-IF4IXT, 1794-OF4IXT, 1794-IF2XOF2IXT 

European Hazardous Location Approval

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical 
equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State 
Controls (Publication 

SGI-1.1

 available from your local Rockwell Automation sales office or online at 

http://literature.rockwellautomation.com

) describes some important differences between solid state 

equipment and hard-wired electromechanical devices.  Because of this difference, and also because 
of the wide variety of uses for solid state equipment, all persons responsible for applying this 
equipment must satisfy themselves that each intended application of this equipment is acceptable.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential 
damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of 
the many variables and requirements associated with any particular installation, Rockwell 
Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and 
diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, 
circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of 
Rockwell Automation, Inc., is prohibited.

Throughout this manual we use notes to make you aware of safety considerations.

WARNING

Identifies information about practices or circumstances that can cause an 
explosion in a hazardous environment, which may lead to personal injury or 
death, property damage, or economic loss.

ATTENTION

Identifies information about practices or circumstances that can lead to 
personal injury or death, property damage, or economic loss. Attentions help 
you:

identify a hazard

avoid a hazard

recognize the consequence

IMPORTANT

Identifies information that is critical for successful application and 
understanding of the product.

ATTENTION

Environment and Enclosure

This equipment is intended for use in a Pollution Degree 2 industrial 
environment, in overvoltage Category II applications (as defined in IEC 
60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according 
to IEC/CISPR 11. Without appropriate precautions, there may be difficulties 
with electromagnetic compatibility in residential and other environments due 
to conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within 
an enclosure that is suitably designed for those specific environmental 
conditions that will be present and appropriately designed to prevent personal 
injury resulting from accessibility to live parts. The enclosure must have 
suitable flame-retardant properties to prevent or minimize the spread of flame, 
complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if 
non-metallic. The interior of the enclosure must be accessible only by the use 
of a tool. Subsequent sections of this publication may contain additional 
information regarding specific enclosure type ratings that are required to 
comply with certain product safety certifications.

In addition to this publication, see:

Industrial Automation Wiring and Grounding Guidelines, for additional 
installation requirements, Allen-Bradley publication 

1770-4.1

.  

NEMA Standards 250 and IEC 60529, as applicable, for explanations of 
the degrees of protection provided by different types of enclosure.

WARNING

If you insert or remove the module while backplane power is on, an electrical 
arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.

WARNING

If you connect or disconnect wiring while the field side power is on, an 
electrical arc can occur. This could cause an explosion in hazardous location 
installations. Be sure that power is removed or the area is nonhazardous 
before proceeding.

ATTENTION

FLEX I/O is grounded through the DIN rail to chassis ground. Use zinc plated 
yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN 
rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are 
poor conductors, can result in improper or intermittent grounding. Secure DIN 
rail to mounting surface approximately every 200 mm (7.8 in.) and use 
end-anchors appropriately. 

ATTENTION

Prevent Electrostatic Discharge

This equipment is sensitive to electrostatic discharge, which can cause internal 
damage and affect normal operation.  Follow these guidelines when you handle 
this equipment:

Touch a grounded object to discharge potential static.

Wear an approved grounding wriststrap.

Do not touch connectors or pins on component boards.

Do not touch circuit components inside the equipment.

Use a static-safe workstation, if available.

Store the equipment in appropriate static-safe packaging when not in 
use.

ATTENTION

Personnel responsible for the application of safety-related programmable 
electronic systems (PES) shall be aware of the safety requirements in the 
application of the system and shall be trained in using the system.

ATTENTION

To comply with the CE Low Voltage Directive (LVD), all connections to this 
equipment must be powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).

ATTENTION

Do not remove or replace a Terminal Base unit while power is applied. 
Interruption of the backplane can result in unintentional operation or machine 
motion.

European Zone 2 Certification (The following applies when the product bears the Ex 
or EEx Marking)

This equipment is intended for use in potentially explosive atmospheres as defined by European 
Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety 
Requirements relating to the design and construction of Category 3 equipment intended for use 
in potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance 
with EN 60079-15 and EN 60079-0.

WARNING

Observe the following additional Zone 2 certification requirements.

This equipment is not resistant to sunlight or other sources of UV 

radiation.

This equipment must be installed in an enclosure providing at least IP54 

protection when applied in Zone 2 environments.

This equipment shall be used within its specified ratings defined by 

Allen-Bradley.

Provision shall be made to prevent the rated voltage from being 

exceeded by transient disturbances of more than 40% when applied in 
Zone 2 environments.

Secure any external connections that mate to this equipment by using 

screws, sliding latches, threaded connectors, or other means provided 
with this product.

Do not disconnect equipment unless power has been removed or the 

area is known to be nonhazardous.

Summary of Contents for FLEX XT I/O 1794-IF2XOF2IXT

Page 1: ...n addition to this publication see Industrial Automation Wiring and Grounding Guidelines for additional installation requirements Allen Bradley publication 1770 4 1 NEMA Standards 250 and IEC 60529 as applicable for explanations of the degrees of protection provided by different types of enclosure WARNING If you insert or remove the module while backplane power is on an electrical arc can occur Th...

Page 2: ...erall temperature code of the system Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation Les produits marqués CL I DIV 2 GP A B C D ne conviennent qu à une utilisation en environnements de Classe I Division 2 Groupes A B C D dangereux et non dangereux Chaque produit est livré avec des marquages sur sa plaque d...

Page 3: ...Current Transmitter Current Input DC only Current Input 2 Wire Current Transmitter Current only Current Input 3 Wire Transmitter DC only Voltage Input I I 51 33 1794 TBN shown 3 Wire Transmitter Word 2 Read Back Channel 2 Word 3 Read Back Channel 3 Word 4 PU FP CF 0 Reserved 0 0 0 0 0 BD DN 0 Word 5 0 0 0 0 P3 P2 P1 P0 0 0 0 0 W3 W2 W1 W0 1794 IF2XOF2XT Word 0 Analog value for Input channel 0 Word...

Page 4: ...5 ms 5 0 ms 0 1 1 0 0 10V 5 0 ms 5 0 ms 0 1 1 1 10V 5 0 ms 5 0 ms 1 0 0 0 0 20 mA 2 5 ms 2 5 ms 1 0 0 1 4 20 mA 7 5 ms 5 0 ms 1 0 1 0 0 10V 2 5 ms 2 5 ms 1 0 1 1 0 5V 2 5 ms 2 5 ms 1 1 0 0 20 mA 2 5 ms 2 5 ms 1 1 0 1 4 20 mA 7 5 ms 5 0 ms 1 1 1 0 10V 2 5 ms 2 5 ms 1 1 1 1 5V 2 5 ms 2 5 ms Configuration Bits MSD LSD Nominal Range Data Type Output Values ModuleUpdate Rate 0 0 0 1 4 20 mA Signed 2 s ...

Page 5: ...or 32 mA continuous one channel at a time Indicators 1 red green power status indicator Isolation voltage 120V continuous Basic Insulation Type when used with 1794 TB2 1794 TB3 1794 TB3S 1794 TB3T or 1794 TB3TS 250V continuous Basic Insulation Type when used with 1794 TBN Type tested at 1500V AC for 60 s and Routine tested at 2550V DC for 1 s between channel to power channel to system and power to...

Page 6: ... at http www ab com for Declaration of Conformity Certificates and other certification details Attribute Value c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File E65584 UL Listed for Class I Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Cont...

Reviews: