    FLEX I/O Digital Input and Output Modules w/ Diagnostics 

Publication 1794-IN096C-EN-P - August 2015

Connecting Wiring for the 1794-OB16D Module

 

(using a 1794-TB2, 1794-TB3, or 1794-TB3S Terminal Base)

1. Connect individual output wiring to numbered terminals on the 0-15 row (A) as 

indicated in the Wiring Connections for 1794-OB16D table.

2. Connect the associated common for each output to the corresponding terminal 

on the 16-33 row (B) as indicated in the Wiring Connections for 1794-OB16D 
table. (The common terminals of row (B) are internally connected together.)

3. CV DC power to terminal 34 on the 34-51 row (C). (The power 

terminals of row (C) are internally connected together.)

4. Connect DC common (COM) to terminal 16 on the 16-33 row (B).

5. If daisychaining power to the next terminal base, connect a jumper from terminal 

51 (+V DC) on this base unit to terminal 34 on the next base unit.

6. If continuing DC common to the next base unit, connect a jumper from terminal 

33 (common) on this base unit to terminal 16 on the next base unit.

1794-TB2, 1794-TB3, and 1794-TB3S Terminal Base Wiring for 1794-OB16D

17      18     19      20      21      22      23     24       25      26      27      28       29      30      31     32       33

0        1        2         3        4        5        6        7        8        9       10      11      12      13      14      15

16

35      36       37      38      39       40     41      42      43       44      45      46      47      48      49      50      51

34

Outputs

Commons

(1794-TB3 shown)

-V (Supply Common) = Terminals B-16 thru B-33
+V (Voltage In) = Terminals C-34 thru C-51

-V

Voltage
In +V

Voltage
Out +V

Voltage

A

B

C

(Use B-33 and C-51 for daisy-chaining to next terminal base unit)

Common

-V

Common

Terminals 35 thru 50 not available on 1794-TB2

Summary of Contents for Flex I/O

Page 1: ...1794 IB16D 1794 OB16D Table of Contents Topic Page Important User Information 2 Environment and Enclosure 3 Preventing Electrostatic Discharge 3 North American Hazardous Location Approval 4 Installing...

Page 2: ...ticular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with...

Page 3: ...igned to prevent personal injury resulting from accessibility to live parts The interior of the enclosure must be accessible only by the use of a tool Subsequent sections of this publication may conta...

Page 4: ...sieurs produits sont combin s dans un syst me le code de temp rature le plus d favorable code de temp rature le plus faible peut tre utilis pour d terminer le code de temp rature global du syst me Les...

Page 5: ...ls for example aluminum or plastic that can corrode oxidize or are poor conductors can result in improper or intermittent grounding Secure DIN rail to mounting surface approximately every 200 mm 7 8 i...

Page 6: ...tor 3 is pushed all the way to the left to connect with the neighboring terminal base adapter You cannot install the module unless the connector is fully extended 3 Make sure the pins on the bottom of...

Page 7: ...d of the input device to the corresponding terminal on the 34 51 row C for each input as indicated in the Wiring Connections for 1794 IB16D table The V2 power terminals of row C are internally connect...

Page 8: ...38 39 40 41 42 43 44 45 46 47 48 49 50 51 34 NC V2 Terminals 43 45 47 and 49 Input Terminals 0 15 Sensor Power Terminals 0 15 V1 COM1 V1 COM1 V1 COM1 V1 COM1 V2 COM2 V2 COM2 V2 COM2 V2 COM2 NC V1 Ter...

Page 9: ...N 00 A 0 B 17 V common connected to terminals 36 38 40 42 44 46 48 and 50 V2 connected to terminals 43 45 47 and 49 IN 01 A 1 B 18 IN 02 A 2 B 19 IN 03 A 3 B 20 IN 04 A 4 B 21 IN 05 A 5 B 22 IN 06 A 6...

Page 10: ...ed together 4 Connect DC common COM to terminal 16 on the 16 33 row B 5 If daisychaining power to the next terminal base connect a jumper from terminal 51 V DC on this base unit to terminal 34 on the...

Page 11: ...0 Output 04 A 4 B 21 Output 05 A 5 B 22 Output 06 A 6 B 23 Output 07 A 7 B 24 Output 08 A 8 B 25 Output 09 A 9 B 26 Output 10 A 10 B 27 Output 11 A 11 B 28 Output 12 A 12 B 29 Output 13 A 13 B 30 Outp...

Page 12: ...FF On Off 0 0 0 0 OFF Short Off Off 0 0 0 0 OFF On Off 0 0 0 0 OFF Normal Off Off 0 0 0 0 OFF On Off 0 0 0 0 OFF ON Open Off RED 1 0 0 1 RED On RED YEL 1 0 0 1 RED Short Off RED 0 1 0 1 RED On RED YEL...

Page 13: ...ED 1 0 0 1 RED On YEL 0 0 0 0 OFF Short Off Off 0 0 0 0 OFF On RED 0 1 0 1 RED Normal Off Off 0 0 0 0 OFF On YEL 0 0 0 0 OFF REV Open Off Off 0 0 1 1 RED On Off 0 0 1 1 RED Short Off Off 0 0 1 1 RED O...

Page 14: ...tect open wire Detect short circuit Sensor power lines Detect open wire 3 Wire Sensor External Power Supply 1794 IB16D 3 Wire Sensor 2 Wire Sensor External Power Supply 1794 IB16D 2 Wire Sensor 3 Wire...

Page 15: ...complementary word for the module Image Table Memory Map for the 1794 IB16D Module Dec 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Oct 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0 Read 1 I15 I14 I13 I12 I11 I10...

Page 16: ...on Filter Time 10 09 08 Filter Time for inputs 0 15 Off to On On to Off 0 0 0 Filter Time 0 Default 0 25 ms 0 0 1 Filter Time 1 0 5 ms 0 1 0 Filter Time 2 1 ms 0 1 1 Filter Time 3 2 ms 1 0 1 Filter Ti...

Page 17: ...ation Type Type tested 2121V DC for 2 s between field side and system No isolation between individual channels Input filter time 1 Off to On On to Off 1 Input off to on filter time is the time from a...

Page 18: ...on Type Type tested at 850V DC for 60 s between field side and system No isolation between individual channels Output signal delay 1 Off to On On to Off 0 5 ms 0 5 ms FlexBus current 60 mA 5V DC Power...

Page 19: ...inal base Wiring category 1 2 on signal ports 1 Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring and Grounding Guidelines publication...

Page 20: ...z Certifications Certifications when product is marked 1 Value c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File E65584 UL Listed for Class I Division 2 Group A B...

Page 21: ...D Input Voltage Sensor Power 1 See the Product Certification link at www ab com for Declarations of Conformity Certificates and other certification details 0 5 10 15 25 20 30 10 20 30 40 50 55 31 2 26...

Page 22: ...erational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures Documentation Feedback Your comments will help us ser...

Reviews: