Allen-Bradley FLEX I/O PROFIBUS 1794-APBDPV1 Installation Instructions Download Page 3

FLEX I/O PROFIBUS Communications Adapter     

3

Publication 1794-IN114A-EN-P - July 2008

2.

Disconnect any wiring jumpered to the adjacent terminal base.

3.

Open the module latching mechanism and remove the module from the 
base unit to which the adapter will be attached.

4.

Push the flexbus connector toward the right side of the terminal base to 
unplug the backplane connection.

5.

Release the locking tab (C) and remove the adapter module.

6.

Before installing the new adapter, notice the notch on the right rear of the 
adapter. This notch accepts the hook on the terminal base unit. The notch 
is open at the bottom. The hook and adjacent connection point keep the 
terminal base and the adapter tight together, reducing the possibility of a 
break in communication over the backplane.

7.

Complete the adapter mounting as follows.
a. Push down and in at the same time to lock the adapter to the DIN rail.

 

If the adapter does not lock in place, use a screwdriver or similar 
device to move the locking tab down while pressing the adapter flush 
onto the DIN rail, and release the locking tab to lock the adapter 
module in place. If necessary, push up on the locking tab to lock.

b. When the adapter is locked onto the DIN rail, gently push the flexbus 

connector into the adapter to complete the backplane.

8.

Reinstall the module in the adjacent terminal base unit.

Connect Wiring for your Module 

1.

Connect the PROFIBUS drop cable to the 9-pin D-shell connector 
according to the following pin assignments.

2.

Connect the cable shield to pin 1.

 

The shield is connected to earth ground.

3.

Connect the data signal pins on both ends ( pin 3 and signal - 
pin 8).

4.

Insert the wired connector into the mating connector on the adapter.

5.

CV DC power to the left side of the lower connector, terminal E.

6.

Connect -V common to the left side of the upper connector, terminal D.

WARNING

If you connect or disconnect the PROFIBUS cable with power applied to this 
module or any device on the network, an electrical arc can occur. This could 
cause an explosion in hazardous location installations. Be sure that power 
is removed or the area is nonhazardous before proceeding.

C

Flexbus connector

44555

44556

C

44557

WARNING

If you connect or disconnect wiring while the field-side power is on, an 
electrical arc can occur. This could cause an explosion in hazardous 
location installations. Be sure that power is removed or the area is 
nonhazardous before proceeding.

PIN

RS-485 Reference

Signal

Description

1

Shield

Shield, RC to earth ground

2

RP

Not used

3

B/B’

RXD/TXD-P

Receive/transmit data - P

4

CTNR-P

Not used

5

C/C’

DGND

Data ground

6

VP

Voltage plus (+5V)

7

RP

Not used

8

A/A’

RXD/TXD-N

Receive/transmit data - N

9

CTNR-N

Not used

Metal shell

Earth ground

ATTENTION

Total power connection wire length must be less than 10 m (32.8 ft).

1

.

.

Data Ground

Shield

Pin #1

5

RCV/ Xmit Data +

9

6

.

.

DROP CABLE

PROFIBUS

 ADAPTER

  Pin #3

Pin #5

+5V Pin #6

Signal -   Pin #8

Earth Ground

RCV/ Xmit Data -

.

*

Pins #5 and #6 can be used to supply an external Profibus terminator.

*

44558

G

E

24

V

COM

PROFIBU

S

 Connector

D

F

44559

Summary of Contents for FLEX I/O PROFIBUS 1794-APBDPV1

Page 1: ... will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts The enclosure must have suitable flame retardant properties to prevent or minimize the spread of flame complying with a flame spread rating of 5VA V2 V1 V0 or equivalent if non metallic The interior of the enclosure must be accessible only by the use of a tool Subsequent sections of th...

Page 2: ...e pour les environnements dangereux Lorsque plusieurs produits sont combinés dans un système le code de température le plus défavorable code de température le plus faible peut être utilisé pour déterminer le code de température global du système Les combinaisons d équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l installation WARNING EXPLOSI...

Page 3: ... connector according to the following pin assignments 2 Connect the cable shield to pin 1 The shield is connected to earth ground 3 Connect the data signal pins on both ends signal pin 3 and signal pin 8 4 Insert the wired connector into the mating connector on the adapter 5 Connect V DC power to the left side of the lower connector terminal E 6 Connect V common to the left side of the upper conne...

Page 4: ...available online at www ab com networks gsd Indicators ATTENTION When connecting wiring torque terminal screws D E F and G to 0 8 Nm 7 lb in ATTENTION Do not wire more than 2 conductors on any single terminal 9 9 44560 Thumbwheel switches for setting the node address Status Indicators Indication Status Off No power Solid green Normal operation Flashing red OFF Recoverable fault FLEX K O module def...

Page 5: ...60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 0 55 C 32 131 F Storage temperature IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration IEC 6...

Reviews: