Allen-Bradley FLEX I/O ControlNet 1794-ACN15 Installation Instructions Manual Download Page 5

FLEX I/O ControlNet Adapter Modules     

5

Publication 1794-IN128E-EN-P - March 2011

 

Wire size

Power connections:

 

Single wire connection: 0.33... 2.5 mm

2

 (22...12 

AWG) solid or stranded  copper wire rated at 75 °C 
(167 °F ) or greater 1.2 mm (3/64 in.) insulation max

Double wire connection: 0.33... 1.3 mm

2

 (22...16 

AWG) solid or stranded (not intermixed) copper wire 
rated at 75 °C (167 °F ) or greater 1.2 mm (3/64 in.) 
insulation max

Wiring Category

(1)

3 – on power ports
2 – on communications ports

North American temp code

T4A

IEC temp code

T4

Enclosure Type Rating

None (open-style)

ControlNet  Cable

Belden RG-6/U 

Weight

220 g (7.76 oz)

Dimensions  

 

HxWxD

87.4 x 94 x 92 mm

 

(3.44 x 3.7 x 3.6 in.)

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation 
Wiring and Grounding Guidelines, publication 

1770-4.1.

Environmental

Attribute

Value

Temperature, 
operating 

IEC 60068-2-1 (Test Ad, Operating Cold),

 

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

 

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

 

-25…55 °C (-13…131 °F)

 

-25 …70 °C (-13…158 °F) – 

1794-ACNR15XT

Temperature, 
surrounding air, max

55 °C (131 °F)

 

70 °C (158 °F) – 

1794-ACNR15XT

Temperature, 
nonoperating

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

 

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),

 

IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal 
Shock):

 

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

 

5 …95% non-condensing

Vibration

IEC60068-2-6 (Test Fc, Operating):

 

5 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

 

30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

 

50 g

Emissions

CISPR 11:

 

Group 1, Class A 

ESD immunity

IEC 61000-4-2:

 

6 kV contact discharges

 

8 kV air discharges

Radiated RF 
immunity

IEC 61000-4-3:

 

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz

 

10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz

 

10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz

 

3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:

 

±2 kV at 5 kHz on power ports

 

±2 kV at 5 kHz on communications ports

Surge transient 
immunity

IEC 61000-4-5:

 

±2 kV line-earth(CM) on communications ports

Conducted RF 
immunity

IEC 61000-4-6:

 

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications (when product is marked)

(1)

Attribute

Value

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. 

See UL File E65584.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, 

certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/EC EMC Directive, compliant with:

 

EN 61326-1; Meas./Control/Lab., Industrial Requirements

 

EN 61000-6-2; Industrial Immunity

 

EN 61000-6-4; Industrial Emissions

 

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with: 

 

AS/NZS CISPR 11; Industrial Emissions

General

Ex

European Union 94/9/EC ATEX Directive, compliant with:

 

EN 60079-15; Potentially Explosive Atmospheres, Protection "n"

 

EN 60079-0; General Requirements 

 

II 3 G Ex nA IIC T4 X

TÜV

TÜV Certified for Functional Safety:

 

Capable of SIL 2

CI

ControlNet Int'l conformance tested to ControlNet specifications

(1)

See the Product Certification link at 

http://www.ab.com

 for Declaration of Conformity, Certificates, 

and other certification details.

Certifications (when product is marked)

(1)

Reviews: