FLEX I/O 240V AC Digital Input and Output Modules
11
Publication 1794-IN123D-EN-P - August 2018
For example, setting bits 00, 01, and 02 as shown below sets the off-to-on filter time for
inputs 00...11 to 12 ms. For other settings, refer to the Input Filter Time table.
To increase the filter time, set the bits according to the table below.
Input Filter Times
Bits
Description
Selected
Filter Time
Maximum Filter Time
(ms)
02
01
00
Filter Time for inputs 00...11
05
04
03
Filter Time for inputs 12...15
Off to On
On to Off
0
0
0
Filter Time 0 (Default)
256
μ
s
7.5
26.5
0
0
1
Filter Time 1
512
μ
s
8
27
0
1
0
Filter Time 2
1 ms
9
28
0
1
1
Filter Time 3
2 ms
10
29
1
0
1
Filter Time 4
4 ms
12
31
1
0
1
Filter Time 5
8 ms
16
35
1
1
0
Filter Time 6
16 ms
24.5
44
1
1
1
Filter Time 7
32 ms
42
60.5
1
0
0
7
6
5
4
3
FLL
I:000
00
Fill File
Source
Destination
Length
#O:010
1
Write FT to
complement of
input module
Write filter time on system startup.
2
1
0
= 44 Octal or 36 Decimal
0
1
0
1
0
0