Allen-Bradley FLEX I/O 1794-OB16 Installation Instructions Manual Download Page 8

8

    FLEX I/O Digital DC Output Modules 

Publication 1794-IN094C-EN-P - July 2015

3. Make sure the pins on the bottom of the module are straight so they will align 

properly with the connector in the terminal base.

4. Position the module (4) with its alignment bar (5) aligned with the groove (6) on 

the terminal base.

5. Press firmly and evenly to seat the module in the terminal base unit. The module 

is seated when the latching mechanism (7) is locked into the module.

Connecting Wiring for the 1794-OB8, 1794-OB8EP, 1794-OB16, and 
1794-OB16P

1. Connect individual output wiring to numbered terminals on the 0-15 row (A) as 

indicated in the table below (1794-OB8 – Terminals 0...7; 1794-OB16 and 
1794-OB16P – terminals 0...15; 1794-OB8EP – even numbered terminals 
0...14).

2. Connect the associated -V output common to the corresponding terminal on the 

16-33 row (B) for each output as indicated in the table below. (Commons are 
internally connected together.)

 

 

1794-OB8EP

 – connect associated output common to odd-numbered terminals 

on row A or associated terminals on row (B).

3. CV DC power to terminal 34 on the 34-51 row (C).

4. Connect -V DC common to terminal 16 on the 16-33 row (B).

5. If daisychaining power to the next terminal base, connect a jumper from terminal 

51 (+V DC) on this base unit to terminal 34 on the next base unit.

6. If continuing -V DC common to the next base unit, connect a jumper from 

terminal 33 (common) on this base unit to terminal 16 on the next base unit.

WARNING: 

If you insert or remove the module while backplane power is on, 

an electrical arc can occur. This could cause an explosion in hazardous 
location installations. Be sure that power is removed or the area is 
nonhazardous before proceeding.

Summary of Contents for FLEX I/O 1794-OB16

Page 1: ...mportant User Information 2 Environment and Enclosure 3 Preventing Electrostatic Discharge 3 European Hazardous Location Approval 4 North American Hazardous Location Approval 5 Installing Your Digital...

Page 2: ...tallation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to...

Page 3: ...event personal injury resulting from accessibility to live parts The interior of the enclosure must be accessible only by the use of a tool Subsequent sections of this publication may contain addition...

Page 4: ...irective The examination and test results are recorded in confidential report No 28 682 010 Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 50021 IM...

Page 5: ...eurs produits sont combin s dans un syst me le code de temp rature le plus d favorable code de temp rature le plus faible peut tre utilis pour d terminer le code de temp rature global du syst me Les c...

Page 6: ...occur This could cause an explosion in hazardous location installations Be sure that power is removed or the area is nonhazardous before proceeding Compatibility The following communication adapters a...

Page 7: ...or 3 is pushed all the way to the left to connect with the neighboring terminal base adapter You cannot install the module unless the connector is fully extended Description Description 1 Keyswitch 5...

Page 8: ...Connect the associated V output common to the corresponding terminal on the 16 33 row B for each output as indicated in the table below Commons are internally connected together 1794 OB8EP connect ass...

Page 9: ...OB16 and 1794 OB16P Outputs 0 15 Output Terminal Common Terminal Output 0 A 0 B 17 Output 1 A 1 B 18 Output 2 A 2 B 19 Output 3 A 3 B 20 Output 4 A 4 B 21 Output 5 A 5 B 22 Output 6 A 6 B 23 Output 7...

Page 10: ...B 4 C 5 Output 3 A 6 A 7 B 23 B 6 C 7 Output 4 A 8 A 9 B 25 B 8 C 9 Output 5 A 10 A 11 B 27 B 10 C 11 Output 6 A 12 A 13 B 29 B 12 C 13 Output 7 A 14 A 15 B 31 B 14 C 15 V DC C 34 to C 51 C 34 and C 5...

Page 11: ...oltage Out V Voltage Terminals 35 thru 50 not available on 1794 TB2 A B C Common V Common Use B 33 and C 51 for daisy chaining to next terminal base unit Total current draw through the terminal base i...

Page 12: ...ctions for 1794 OB32P table 5 Connect the associated power to the V2 terminal 43 45 47 or 49 on the 34 51 row C as indicated in the Wiring Connections for 1794 OB32P table 6 Connect the associated out...

Page 13: ...Base Unit Output Output Terminal Common Power Output 0 A 0 Connect common to terminals 36 38 40 and 42 Connect power to terminals 35 37 39 and 41 Output 1 A 1 Output 2 A 2 Output 3 A 3 Output 4 A 4 O...

Page 14: ...t 24 B 25 Output 25 B 26 Output 26 B 27 Output 27 B 28 Output 28 B 29 Output 29 B 30 Output 30 B 31 Output 31 B 32 For Outputs 0 15 use V1 and COM1 V1 DC power Power terminals 35 37 39 and 41 Com1 DC...

Page 15: ...0 corresponds to output 0 O1 corresponds to output 1 and so on F Overload fault bit 1 fault present 0 no fault FR Fault reset bit 1 reset output 0 no change Note The unused lower byte in read word 1 f...

Page 16: ...ont of the module or toggle the output reset bit write word 1 bit 08 or cycle backplane power Using the Reset Button on the 1794 OB8EP When you press the reset button the fault indicator for the fault...

Page 17: ...OB8 1794 OB16 1794OB16P and 1794 OB32P Modules Dec 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Oct 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0 Read Not used Write O15 O14 O13 O12 O11 O10 O9 O8 O7 O6 O5 O4 O3 O...

Page 18: ...current max 0 5 mA Isolation voltage 50V continuous Basic Insulation Type Tested at 850V DC for 1 s between user and system No isolation between individual channels Output signal delay 1 Off to On On...

Page 19: ...or 50 ms repeatable every 3 seconds Off state leakage current max 0 5 mA Isolation voltage 50V continuous Basic Insulation Type Tested at 850V DC for 1 s between field side and system No isolation bet...

Page 20: ...epeatable every 2 seconds Off state leakage current max 0 5 mA Isolation voltage 50V continuous Basic Insulation Type Tested at 850V DC for 1 s between user and system No isolation between individual...

Page 21: ...r 50 ms repeatable every 2 seconds Off state leakage current max 0 5 mA Isolation voltage 50V continuous Basic Insulation Type Type tested at 850V DC for 60 s between field side and system No isolatio...

Page 22: ...wer supply current 1794 OB8 25 mA 24V DC 10 35 mA 1794 OB8EP 80 mA 24V DC 1794 OB16 49 mA 24V DC 20 65 mA 1794 OB16P 60 mA 24V DC 25 75 mA see Derating Curve 1794 OB32P 219 mA 24V DC 104 mA 10V DC 278...

Page 23: ...ibration IEC60068 2 6 Test Fc Operating 5 g 10 500 Hz Shock operating IEC60068 2 27 Test Ea Unpackaged shock 30 g Shock nonoperating IEC60068 2 27 Test Ea Unpackaged shock 50 g Emissions CISPR 11 Grou...

Page 24: ...lue c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File E65584 UL Listed for Class I Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL...

Page 25: ...n DEMKO 14ATEX1342501X II 3 G Ex nA IIC T4 Gc 1794 OB8EP III 3 G Ex nA IIC T3 Gc 1794 OB16P EC 60079 0 6th Edition IEC 60079 15 4th Edition T V 1794 OB8EP 1794 OB16 1794 OB16P only T V Certified for F...

Page 26: ...ve represents the safe operating range for the module under various conditions of user supplied 24V DC supply voltages and ambienttemperatures Normal mounting safe operating range includes Other mount...

Page 27: ...FLEX I O Digital DC Output Modules 27 Publication 1794 IN094C EN P July 2015 Notes...

Page 28: ...operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures Documentation Feedback Your comments will help us s...

Reviews: