8
FLEX Ex 24V dc Non-Isolated Source 4 Output Module
Publication
1797-5.6 - December 2003
2.
Connect the associated output to the corresponding (-) terminal (1, 5,
9, 13) on the 0-15 row (A) for each output as indicated in the table
below.
3.
CV dc power to terminal 34 on the 34-51 row (C).
4.
Connect -V to terminal 35 on the 34-51 row (C).
5.
If continuing power to the next terminal base unit, connect a jumper
from terminal 50 (+V) on this base unit to terminal 34 on the next
base unit.
6.
If continuing common to the next terminal base unit, connect a
jumper from terminal 51 (-V) on this base unit to terminal 35 on the
next base unit.
WARNING
Make certain that you power this module with an intrinsically
safe power supply. Do not exceed the values listed in the
specifications for this module.
If you connect or disconnect wiring while the field-side power is
on, an electrical arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is removed
or the area is nonhazardous before proceeding.