1761-6.5
DNI Configuration Parameters and Programming Notes
5-13
Device Type
Select the device connected to the DNI’s RS-232 port. If you are connecting
an Allen-Bradley controller as a DeviceNet I/O slave device, this selection
is used by the DNI to determine the type of communication commands used
to read and write data.
To achieve the best communications performance you should use the
following combinations:
Parameter
Type
Parameter Number
Description Range
Default Value
Series A Series B
I/O
14
11
DF1 Device 0 to 3:
0: Other
1: PLC
2: SLC/ Other
MicroLogix
3: MicroLogix 1000
3 = MicroLogix
1000
RS-232 Device
DF1 Device
Value
File Type
File Number
MicroLogix 1000
3
N (integer)
7
SLC 5/03 or higher
Other MicroLogix (i.e. MicroLogix
1500)
2
N (integer)
9
Note:
If you do not want to communicate with these specific data files,
RS-232 port communications throughput will suffer marginally.