24
ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module
Publication
1797-IN015G-EN-P - August 2017
Module Indicators
The following explains the indications seen on the 1797-RPA and
1797-RPFM modules.
1797-RPA Indicators
The figure below identifies indicators on the repeater adapter.
Power Indicator
Comm and Module Status Indicators for the 1797-RPA Module
If
This Indicates
Steady Green
Power is applied.
Off
No power is applied.
If Both Are
This Indicates
Alternately
Red/Green
The adapter is being powered-up or reset. The LEDs alternately
flash red and green for about 5 s.
Steady Green
Normal operation.
Off
The unit is not powered. Check the module power status.
Red
There is an adapter fault.
If the fault indication is caused by a jabber condition, the fault
indication will automatically be cleared when the jabber condition
is removed from the coax or fiber port.
If a jabber condition is not causing the fault, replace the repeater
adapter.
1
3
2
4
+V
+V
-V
-V
1797-RPA
PWR
REPEATER
ADAPTER
COMM
STATUS
MODULE
STATUS
41174
Module Power Status
Comm Status
Module Status
1797-RPA