14
ControlNet Fiber-optic Ring Repeater Modules
Rockwell Automation Publication 1786-IN003D-EN-P - April 2011
6.
Remove the protective backplane cap as shown on
page 18
.
7.
Once the modules are attached to the DIN rail, slide them together to
mate the repeater adapter with the repeater module.
WARNING:
Removal and insertion under power (RIUP) is not
supported. These modules must be powered down while
connecting and disconnecting them from any interconnected
modules.
If you insert or remove the module while backplane power is on, an
electrical arc can occur. This could cause an explosion in hazardous
location installations.
Be sure that power is removed or the area is nonhazardous before
proceeding.
WARNING:
When you connect or disconnect the removable
terminal block (RTB) with field side power applied, an electrical arc
can occur. This could cause an explosion in hazardous location
installations.
Be sure that power is removed or the area is nonhazardous before
proceeding.
42632