14
Publication 1747-5.41
Amber
0000
through
9999
Adapter is
running Power
On Self Test.
None
None
Amber
A/A
Adapter is
displaying
Series and
Revision level.
None
None
Amber
INIT
Adapter is
loading and
initializing
operating
system.
None
None
Solid Red
FATL
Number
Number
Module is not
communicating.
The Adapter has
either failed a
hardware test, or
gone into a state
from which it
cannot recover.
The two numbers
following the FATL
describe the
problem in detail.
Document the two
numbers. Power
cycle the adapter.
Contact Allen-
Bradley service.
Flashing
Green
PWR UP
Module is not
communicating.
The application
program in the
adapter has just
started.
None
Flashing
Red
A#00 ERR
Module is not
communicating.
The node address
switches are set to
00 which is not
valid.
Power the adapter
off, remove the
adapter from the
chassis, change the
node address switch
to something other
than 00, replace the
adapter in the
chassis, and apply
power.
Flashing
Red
NET ERR
Module is not
communicating.
The adapter has
not detected a
valid ControlNet
network on either
channel A or B.
Check ControlNet
cables.
OK LED
Display
Description
Probable Cause
Recommended
Action