CSA Hazardous Location Approval
Conductors
Wire Size
Category
22-14-gauge (2mm
2
) stranded
1
3/64 inch (1.2mm) insulation maximum
1
2, 3
Screwdriver Width for RTB
5/16 inch (8mm) maximum
User Manual
Publication 1756-6.5.8
Agency Certification
(when product or packaging is marked)
1
Maximum wire size will require extended housing - 1756-TBE.
2
Use this conductor category information for planning conductor routing as described in
the system level installation manual.
3
Refer to publication 1770-4.1, "Programmable Controller Wiring and Grounding Guidelines”
4
CSA certification–Class I, Division 2, Group A, B, C, D or nonhazardous locations.
FM approved–Class I, Division 2, Group A, B, C, D or nonhazardous locations.
CSA certifies products for general use as well as for use in hazardous locations. Actual CSA certification is
indicated by the product label as shown below, and not by statements in any user documentation.
Example of the CSA certification product label:
To comply with CSA certification for use in hazardous locations, the following information becomes a part of
the product literature for this CSA-certified industrial constrol product::
•
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D, or non-hazardous locations only.
•
The products having the appropriate CSA markings (that is, Class I, Division 2, Groups A, B, C, D) are
certified for use in other equipment where the suitability of combination (that is, application or use) is
determined by the CSA or the local inspection office having jurisdiction.
IMPORTANT
Due to the modular nature of a programmable control system, the product with the
highest temperature rating determines the overall temperature code rating of a
programmable control system in a Class I, Division 2 location. The temperature code
rating is marked on the product label as shown.
marked for all applicable directives
Class I Div 2 Hazardous
4
Class I Div 2 Hazardous
4
marked for all applicable acts
N223
CL I, DIV 2
GP A,B,C,D