Publication 1756-UM001E-EN-P - August 2002
11-14
Communicate with Another Controller over a ControlNet
™
Network
Step 6: Configure the
Message
A.
In the MSG instruction, click
.
B.
Select a configuration for the message:
...
Table 11.A Message to a ControlLogix or FlexLogix controller
If you want to:
For this item:
Type or select:
read (receive) the data
Message Type
CIP Data Table Read
Source Element
first element of the tag that contains data in the other controller
Number Of Elements
number of elements to transfer
Destination Tag
first element of the tag (controller-scoped) in this controller for the data
write (send) the data
Message Type
CIP Data Table Write
Source Tag
first element of the tag (controller-scoped) in this controller that
contains the data
Number Of Elements
number of elements to transfer
Destination Element
first element of the tag for the data in the other controller
Table 11.B Message to a PLC-5 controller
If the data is:
And you want to:
For this item:
Type or select:
integer (s)
read (receive) data
Message Type
PLC5 Typed Read
Source Element
data table address in the PLC-5 controller (e.g., N7:10)
Number Of Elements
number of integers to transfer
Destination Tag
first element of
int_buffer
write (send) data
Message Type
PLC5 Typed Write
Source Tag
first element of
int_buffer
Number Of Elements
number of integers to transfer
Destination Element
data table address in the PLC-5 controller (e.g., N7:10)
floating-point (REAL)
read (receive) data
Message Type
PLC5 Typed Read
Source Element
data table address in the PLC-5 controller (e.g., F8:0)
Number Of Elements
number of values to transfer
Destination Tag
first element of the tag (controller-scoped) in this
controller for the data
write (send) data
Message Type
PLC5 Typed Write
Source Tag
first element of the tag (controller-scoped) in this
controller that contains the data
Number Of Elements
number of values to transfer
Destination Element
data table address in the PLC-5 controller (e.g., F8:0)
Summary of Contents for controllogix 1756-L63
Page 1: ...ControlLogix System 1756 L1 L1Mx L55Mxx L63 User Manual Allen Bradley HMIs...
Page 4: ...Publication 1756 UM001E EN P August 2002 Summary of Changes 2 Notes...
Page 16: ...Publication 1756 UM001E EN P August 2002 Table of Contents x...
Page 268: ...Publication 1756 UM001E EN P August 2002 15 4 Monitor Connections Notes...
Page 276: ...Publication 1756 UM001E EN P August 2002 16 8 Communicate with a DeviceNet Device Notes...
Page 402: ...Publication 1756 UM001E EN P August 2002 24 22 Program Motion Control Notes...
Page 408: ...Publication 1756 UM001E EN P August 2002 25 6 Maintain the 1756 BA1 Battery Notes...
Page 418: ...Publication 1756 UM001E EN P August 2002 B 2 Estimate Execution Time...
Page 420: ...Publication 1756 UM001E EN P August 2002 C 2 Estimate Memory Use...
Page 422: ...Publication 1756 UM001E EN P August 2002 D 2 Determine When Data Is Updated Notes...
Page 424: ...Publication 1756 UM001E EN P August 2002 E 2 Reconfigure an I O module Notes...
Page 428: ...Publication 1756 UM001E EN P August 2002 4 Index...
Page 429: ...Publication 1756 UM001E EN P August 2002 Index 5 Allen Bradley HMIs...
Page 430: ...Publication 1756 UM001E EN P August 2002 6 Index...
Page 435: ...ControlLogix System User Manual Allen Bradley HMIs...