Publication 1790-UM003A-EN-P - May 2002
Installation and Wiring
2-15
4.
At the other end of the cable, cut the drain wire and foil shield
back to the cable and apply shrink wrap.
5.
Connect the signal wires to the terminal block. Connect the other
end of the cable to the analog input device.
6.
Repeat steps 1 through 5 for each channel on the module.
Wiring the Terminal Blocks
The following figures show how to wire the terminal blocks.
Figure 2.1 1790D-4R0-RTD Input Module D-Shell Wiring
Figure 2.2 1790D-T4R0 and 179P-T4R0 RTD Input Module D-Shell Wiring
TIP
See Appendix D
Using Thermocouple Junctions
for
additional information on wiring grounded,
ungrounded, and exposed thermocouple types.
IMPORTANT
When using an ungrounded thermocouple, the shield
must be connected to ground at the module end.
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
+24V
NC
NC
NC
CH0_A
CH0_B
CH1_A
CH1_B
NC
NC
CH2_A
CH2_B
CH3_A
CH3-B
NC
NC
NC
GND
GND
+24V
+24V
GND
NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
Wire pins 17, 18, 19 to Field Power (+) 24V dc
Wire pins 35, 36, 37 to Field Power (-) GND
43256
20
18
16
14
12
10
8
6
4
2
19
17
15
13
11
9
7
5
3
1
NC
NC
CH3_B
NC
CH0-B
NC
NC
CH2_B
CH1_B
GND
NC
NC
CH2_A
CH1_A
+24V
NC
NC
CH3_A
NC
CH0_A
432X1
Wire pin 1 to Field Power (+) 24V dc
Wire pin 2 to Field Power (-) GND
Summary of Contents for CompactBlock LDX 1790D-4T0
Page 2: ......
Page 8: ...Publication 1790 UM003A EN P May 2002 viii ...
Page 50: ...Publication 1790 UM003A EN P 3 20 Module Data Status and Channel Configuration for DeviceNet ...
Page 56: ...Publication 1790 UM003A EN P 4 6 Diagnostics and Troubleshooting ...
Page 102: ...Publication 1790 UM003A EN P G 4 ...
Page 108: ...Publication 1790 UM003A EN P May 2002 I 6 ...
Page 111: ...AB Drives ...