Rockwell Automation Publication 5069-IN010B-EN-P - November 2017
9
COMPACT 5000 Analog 8-channel Current/Voltage Input Module
Wire the Removable Terminal Block
1. Confirm that MOD power and all sources of SA power are
turned off.
2. Strip insulation from the wires that you connect to the RTB.
3. Connect the wire to the terminal.
Disconnect Wires from the Removable Terminal Block
Disconnect wires from the RTB.
WARNING:
If you connect or disconnect wiring while power is
applied, an electric arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is removed or
the area is nonhazardous before proceeding.
RTB Type
Action
Screw
Strip12 mm (0.47 in.) of insulation from the wires.
Spring
Strip 10 mm (0.39 in.) of insulation from the wires.
RTB Type
Action
Screw
1. Insert the wire into the terminal.
2. Turn the screwdriver to close the terminal on the wire. Torque the
screw to 0.4 N•m (3.5 lb•in).
Spring
Push the wire into the terminal.
If the wire is too thin, crimp a wire ferrule on the wire and insert it.
5069-RTB18-SPRING RTB
5069-RTB18-SCREW RTB
WARNING:
If you connect or disconnect wiring while power is
applied, an electric arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is removed or
the area is nonhazardous before proceeding.
RTB Type
Action
Screw
1. Turn the screwdriver counter-clockwise to open the terminal.
2. Remove the wire.
Spring
1. Insert and hold a screwdriver in the right-side terminal.
2. Remove the wire.
3. Pull out the screwdriver.
5069-RTB18-SCREW RTB