Publication 1769-UM005A-EN-P
Configuring the 1769-IR6 RTD Module with the Generic Profile for CompactLogix Controllers using RSLogix5000
C-3
This screen narrows your search for I/O modules to configure into your
system. With the initial release of the CompactLogix5320 controller, this
screen only includes the “Generic 1769 Module”. Click the OK button and
the following default Generic Profile screen appears:
This is the default Generic Profile screen. First, select the Comm Format
(“Input Data – INT” for the 1769-IR6), then fill in the name field. In this
example, “IR6” is used to help identify the module type in the Controller
Organizer. The Description field is optional and may be used to provide
more details concerning this I/O module in your application.
The slot number must be selected next, although it begins with the first
available slot number, 1, and increments automatically for each
subsequent Generic Profile you configure. In this example, the 1769-IR6
RTD Input module is located in slot 1.
The Comm Format, Assembly Instance and Size values can be found in
the following table for the 1769-IR6 RTD Input module:
Note the Assembly Instance numbers and their associated sizes for the
1769-IR6 module and enter them into the Generic Profile. The Generic
Profile for a 1769-IR6 should look like the following:
Comm Format
Parameter
Assembly
Instance
Size
(16-bit)
Input Data – INT
Input
Output
Config
101
104
102
8
0
8
Summary of Contents for Compact 1769-IR6
Page 1: ...Compact I O RTD resistance Input Module Catalog Number 1769 IR6 User Manual AB PLCs ...
Page 10: ...Publication 1769 UM005A EN P P 4 ...
Page 40: ...Publication 1769 UM005A EN P 3 16 Installation and Wiring ...
Page 74: ...Publication 1769 UM005A EN P 4 34 Module Data Status and Channel Configuration ...
Page 115: ...AB PLCs ...