120
Rockwell Automation Publication 2100-IN012G-EN-P - August 2016
Appendix A
Bulletin 140G Unit Assembly Instructions
7. Place the circuit breaker in the ON position.
Use a large slotted screwdriver (we recommend a 3/8 or 1/2 in. wide
blade) to remove the bale.
8. To remove the bale, on the top side of the bale, place the screwdriver flat
on the side and rotate the screwdriver.
9. Disconnect the circuit breaker wiring.
a. Remove terminal cover mounting screw and slide the terminal cover
forward (click when pulling).
b. To remove the line side connection use an allen wrench (G and H-
frame 5 mm hex, J-frame 6 mm).
Make note of the phasing of the cables.
c. To remove the load side connection use an allen wrench (G and H-
frame 5 mm hex, J-frame 6 mm).
10. To remove the circuit breaker, remove two Phillips screws.
Save the lock washers and screws.
Line Side Wiring
Load Side Wiring
Circuit Breaker
Mounting Screws
Bale