Allen-Bradley ArmorBlock 1732E-8IOLM12R Wiring Diagrams Download Page 2

2

    ArmorBlock IO-Link Master Module 

Publication

 1732E-WD008A-EN-P - July 2016

EtherNet/IP Connector

D-Code Micro Network Female Connector 

Auxiliary Power Connector

Auxiliary Power Micro-style 4-Pin Receptacles   

IMPORTANT

The maximum current that any pin on the power connectors can carry is 4 A.

ATTENTION: 

To comply with the CE Low Voltage Directive (LVD), this 

equipment and all connected I/O must be powered from a source compliant 
with the following:

Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).

ATTENTION: 

To comply with UL restrictions, this equipment must be 

powered from a source compliant with the following: Limited Voltage.

Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).

ATTENTION: 

This equipment is considered Group 1, Class A industrial 

equipment according to IEC/CISPR 11. Without appropriate precautions, 
there may be difficulties with electromagnetic compatibility in residential 
and other environments due to conducted and radiated disturbance.

(View into connector 1)

Pin 1

Pin 2  

Pin 3  M12_Tx-

Pin 4  M12_Rx-

Pin 5  Connector shell       
shield GND

4

2

3

1

5

44808

(View into connector 2)

Pin 1

Pin 2  

Pin 3  M12_Rx-

Pin 4  M12_Tx-

Pin 5  Connector shell       
shield GND

1

4

3

2

Male Input

Female Output

(View into receptacle)

Pin 1

Auxiliary power+

Pin 2

Module/sensor power+

Pin 3

Module/sensor power-

Pin 4

Auxiliary power-

45764

3

4

1

2

45763