2
ArmorBlock IO-Link Master Module
Publication
1732E-WD008A-EN-P - July 2016
EtherNet/IP Connector
D-Code Micro Network Female Connector
Auxiliary Power Connector
Auxiliary Power Micro-style 4-Pin Receptacles
IMPORTANT
The maximum current that any pin on the power connectors can carry is 4 A.
ATTENTION:
To comply with the CE Low Voltage Directive (LVD), this
equipment and all connected I/O must be powered from a source compliant
with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
ATTENTION:
To comply with UL restrictions, this equipment must be
powered from a source compliant with the following: Limited Voltage.
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
ATTENTION:
This equipment is considered Group 1, Class A industrial
equipment according to IEC/CISPR 11. Without appropriate precautions,
there may be difficulties with electromagnetic compatibility in residential
and other environments due to conducted and radiated disturbance.
(View into connector 1)
Pin 1
Pin 2
Pin 3 M12_Tx-
Pin 4 M12_Rx-
Pin 5 Connector shell
shield GND
4
2
3
1
5
44808
(View into connector 2)
Pin 1
Pin 2
Pin 3 M12_Rx-
Pin 4 M12_Tx-
Pin 5 Connector shell
shield GND
1
4
3
2
Male Input
Female Output
(View into receptacle)
Pin 1
Auxiliary power+
Pin 2
Module/sensor power+
Pin 3
Module/sensor power-
Pin 4
Auxiliary power-
45764
3
4
1
2
45763