Allen-Bradley ArmorBlock 1732E-8IOLM12R Wiring Diagrams Download Page 1

Wiring Diagrams

ArmorBlock IO-Link Master Module

Catalog Numbers 1732E-8IOLM12R

Parts List

Your package contains one 1732E ArmorBlock™ module, a set of label markers, 
and these pinout guide wiring instructions.

For complete installation instructions, refer to the Module Publication Number 
table and visit 

http://www.rockwellautomation.com/literature/

.

   

I/O Connectors

Micro-style 5-Pin I/O Female Connector 

Module Publication Number

Module

Publication Number

ArmorBlock I/O 8 Channel IO-Link Master Module 
Installation Instructions

1732E-IN001

ATTENTION: 

This equipment is intended for use in a Pollution Degree 2 

industrial environment

ATTENTION: 

Two sets of mounting holes are used to mount the module 

directly to a panel or machine. Mounting holes accommodate #8 (M4) pan 
head screws. The torque specification is 0.68 Nm (6 lb-in.).

3

4

1

2

5

45762

(View into connector)

Pin 1

Sensor source voltage

Pin 2

IO-Link, Input/output B

Pin 3

Return

Pin 4

IO-Link, Input/output A

Pin 5

PE