After wiring has been completed, check that all wires are in the wiring 

cavity of the terminal block so they will not interfere with the switch 

when it is plugged into the terminal block.
Recheck all wiring terminal screws for tightness.

Note

: For switches that have been factory wired, check wire color and 

their position in the terminal block for proper circuit hookup.
• Grounding of switch should be achieved per National Electric 

Code (NFPA 70) requirements. Grounding terminal is located in 

the terminal block  housing.

• Arrange control wiring according to terminal  markings.
• Tighten terminal screws according to specifications.
• Only use insulated connectors.

Actuator Head Positioning

The actuator head may be placed in any of four positions on the switch 

body. Loosen the four captive screws. Place the

 

head in the desired 

position and securely re-tighten the four screws (see figure below).

Lever Positioning

The lever on rotary actuated devices is adjustable to any position 

through 360° around the shaft. Loosen the nut, move the lever to the 

desired position and securely re-tighten the nut (see figure below).

Changing Direction of Actuation

The switch action of lever operated limit switches may be adjusted to 

operate in either a clockwise, a counterclockwise, or both directions 

movement of the shaft.
To change the actuation direction, follow the steps below:

Step 1

: Loosen the four head mounting screws and remove the 

operating head from the switch body.

Step 2

: Locate the plunger on the underside of the operating head.

Step 3

:   Pull the plunger outward and rotate it in steps of 90 ° to 

provide the operating mode desired. The respective settings are shown 

in the figure below.

Step 4

:   Make sure the plunger is pushed back inward and

 

the “O” ring 

is properly seated before the operating head is reattached to the switch 

body.

Step 5

: Securely re-tighten the operating head mounting screws.

Step 6

:   Check for the desired actuation mode.

Methods of Actuation Examples

IMPORTANT

Pay close attention to the terminal numbering on the 
terminal block when wiring this switch. Terminals 1 and 2 or 
5 and 6 are normally open contacts.
Terminals 3 and 4 or 7 and 8 are normally closed contacts.

IMPORTANT

This procedure must be performed in a clean environment to 
avoid the introduction of foreign material into the operating 
mechanism.

802T–APD

802T–W1A 1.5 in. long

90  Non-overtravel Dog

802T–DPD

Top Push Roller

30   Non-overtravel Dog

802T–KPD

Side Push Roller

30   Non-overtravel Dog

Vmax = 30 ft/min @ actuator

F max = 150 cycles/min