Rockwell Automation Publication 5069-UM004A-EN-P - April 2019
89
Input Module Features
Chapter 3
Compact 5000 I/O Safety Input Module
lists tags that are used on Compact 5000 I/O safety input module.
For more information on fault reporting, see Appendix A,
IMPORTANT
For more information on the valid values for each tag, see Appendix B,
Module Tag Definitions on page 231
.
Table 14 - Compact 5000 I/O Safety Input Module - Fault and Data Status
Data Type
Tag Name
Triggering Event That Sets
Fault
ConnectionFaulted
(1)
The owner-controller loses its connection to the module.
Ptxx.Fault
The point data quality is bad or the channel is set to Not Used.
Ptxx.ShortCircuit
A short circuit condition exists on the point.
Testxx.Fault
The point data quality is bad or the channel is set to Not Used.
Testxx.ShortCircuit
A short circuit condition exists on the test point.
Testxx.FieldPowerOff
A field power lost condition exists on the test point.
Status
RunMode
The module is in Run Mode.
DiagnosticActive
Indicates if any diagnostics are active or if the prognostics threshold is reached.
DiagnosticSequenceCount
The count increments each time that a diagnostic condition is detected or removed.
Ptxx.Data
The data currently at the point.
Ptxx.Uncertain
The point data can be imperfect because an Over temperature or Critical Temperature condition exists.
Ptxx.Status
The point state transitions from normal to faulted or faulted to normal.
Testxx.Readback
A 24V DC power is present at the test output.
Testxx.Uncertain
The test point data can be imperfect.
Testxx.Status
The test point state transitions from normal to faulted or faulted to normal.
(1) This tag provides module-wide data an affects all channels simultaneously.