168
Rockwell Automation Publication 5069-UM004A-EN-P - April 2019
Chapter 6
Configure a Standard Module
Edit 5069-IB16 Module
Configuration Categories
To configure a 5069-IB16K module, you use the 5069-IB16 module profile in
your Logix Designer application project.
In addition to the General, Connection, and Module Info categories, the
following categories are available when you configure a 5069-IB16 module:
•
•
Counters Category
The Counters category is only available if you choose a value for Counters in
the Module Definition dialog box.
The Counters category shows the configuration options available for each
counter. You can also configure the counter Preset value and enable Rollover at
Preset.
IMPORTANT
If you use the Listen Only connection type, the Points Category and Counters
Category do not appear.
IMPORTANT
The total number of Counters subtracts from the available number of Points.
For example, if you configure a 5069-IB16 module to use four counters, the
first four terminals are not available to use as points.
The number of points available on the module in this case is 12. That is,
points 4…15.
The maximum number of counters that can be configured is eight channels.
That is, counters 0…7.