Rockwell Automation Publication 5069-UM004A-EN-P - April 2019
155
Configure a Standard Module
Chapter 6
Discover Remote I/O Modules
To use the Discover Modules method with remote I/O modules, complete the
following steps.
1. Go online with your Logix Designer application.
The project must include a Compact 5000 I/O EtherNet/IP adapter.
2. Right-click the Compact 5000 I/O EtherNet/IP adapter and choose
Discover Modules.
The Logix Designer application automatically detects available modules
that are connected to the backplane.
3. At the Select Module Type window, click Create to add the discovered
module to your project.