Chapter 4
Output Module Features
Compact 5000 I/O Safety Output Modules
lists tags that are used on Compact 5000 I/O safety output modules.
For more information on fault reporting, see Appendix A,
IMPORTANT
For more information on the valid values for each tag in
Module Tag Definitions on page 231
Table 39 - Compact 5000 I/O Safety Output Modules - Fault and Data Status
Data Type
Tag Name
Triggering Event That Sets
Fault
ConnectionFaulted
(1)
The owner-controller loses its connection to the module.
Ptxx.Fault
The point data quality is bad or the channel is set to Not Used.
Ptxx.ShortCircuit
A short circuit condition exists on the point.
Ptxx.FieldPowerOff
A field power lost condition exists on the point.
Status
RunMode
The module is in Run Mode.
DiagnosticActive
Indicates if any diagnostics are active or if the prognostics threshold is
reached.
DiagnosticSequenceCount
The count increments each time that a diagnostic condition is detected
or removed.
Ptxx.Readback
A 24V DC power source is connected to the output circuit.
Ptxx.Data
The data currently at the point.
Ptxx.Uncertain
The point data can be imperfect.
(1) This tag provides module-wide data an affects all channels simultaneously.