The EtherNet/IP communication auxiliary module provides parameters to let
you view the status and configure the DeviceNet scanner with RSNetWorx™
for DeviceNet if you do not want to use the internal web server of the
EtherNet/IP communication auxiliary module.
lists the 14 available
parameters.
Table 10 - Parameter List
Parameter Programming
Parameter Listing
The details for each of the 14 available parameters are listed below.
Table 11 - Parameter 1 — Scanner Status
1
Scanner Status
8
SL Entry Size
2
SL Entry 1 Status
9
Device Keys
3
SL Entry 2 Status
10 Scanlist Config
4
SL Entry 3 Status
11 ADR Record
5
SL Entry 4 Status
12 ADR Enable
6
SL Entry 5 Status
13 DNet IO RPI
7
SL Entry 6 Status
14 DNet IO Inhibit
IMPORTANT
Parameter setting changes to the EtherNet/IP communication auxiliary
module take effect immediately even during a “running” status.
Description
Access Rule
Data Type
Units
Value
Min.
Max. Default
Provides the status of the
Devicenet scanner.
Get
WORD
—
0
16383
0
Bit
0 On Line
3 No Scanner Messages
6 Initializing
1 Illegal Scan List
4 Transmit Failure
7 Duplicate MAC Failure
2 No Network Messages
5 In Idle Mode
8 Bus Off
Summary of Contents for 193-DNENCAT
Page 6: ...6 Rockwell Automation Publication 193 UM014C EN P August 2016 Table of Contents Notes...
Page 8: ...8 Rockwell Automation Publication 193 UM014C EN P August 2016 Summary of Changes Notes...
Page 10: ...10 Rockwell Automation Publication 193 UM014C EN P August 2016 Preface Notes...
Page 80: ...80 Rockwell Automation Publication 193 UM014C EN P August 2016 Chapter 8 Email Text Notes...
Page 111: ......