Allen-Bradley 1794-OW8 Installation Instructions Download Page 4

Publication 1794-IN019E-EN-P - May 2009 

4

 PN-46788

Supersedes Publication 1794-IN019D-EN-P - June 2004

Copyright © 2009 Rockwell Automation, Inc. All rights reserved.

General

Attribute

Value

Outputs per module

1 group of 8 Form A isolated (normally open)

 

electromechanical relays

Module location

Mounts on 1794-TB2, -TB3, -TB3S, -TBN and -TBNF Terminal Base Units.
When using 1794-TBNF terminal base unit, use 3.0 A, 250V AC 
slow-blow fuses (Littelfuse pt. no. 239003)

Off-State leakage

 

current (max at 240V AC)

1.0m A thru snubber circuit

Minimum contact load

100

μ

A at 100mV DC

Output voltage range (load 
dependent)

5-30V DC @ 2.0 A resistive

 

125V DC @ 0.22 A resistive

 

125V AC @ 2.0 A resistive

 

240V AC @ 2.0 A resistive
If used in European Zone 2 potentially explosive atmospheres:

 

1794-OW8 - voltages must be at or below 60V AC or 75V DC; 

 

1794-OW8K - voltages must be at or below all voltage ratings.

Output current rating 

 

(at rated power)

Resistive

 

2 A @ 5-30V DC

 

0.22 A @ 125V DC

 

2 A @ 125V AC

 

2 A @ 240V AC

 

Inductive

 

0.98 A steady state @ 5-30V DC, L/R = 7ms

 

0.5 A steady state @ 48V DC, L/R = 7ms

 

0.22 A steady state @ 125V DC, L/R = 7ms

 

2.0 A steady state, 15A make @ 120V AC, 

 

PF = cos 

θ

 = 0.35

 

2.0 A steady state, 7.5A make @ 240V AC, 

 

PF = cos 

θ

 = 0.35

Power rating 

 

(steady state)

250W max. for 125V AC resistive output

 

480W max. for 240V AC resistive output

 

60W max. for 30V DC resistive output

 

27W max. for 125V DC resistive output

 

180VA max. for 125V AC inductive output

 

180VA max. for 240V AC inductive output

 

27VA max. for 30V DC inductive output

 

27VA max. for 125V DC inductive output

Output signal delay

 

OFF to ON

 

ON to OFF

10ms maximum (time from valid output on signal to relay energization by 
module)

 

10ms maximum (time from valid output off signal to relay deenergization 
by module)

Initial contact resistance

30m

Ω

Switching frequency

1 operation/3s (0.3Hz at rated load) max

Bounce time

1.2ms (mean)

Expected life of

 

electrical contacts

Minimum 100,000 operations @ rated loads

Flexbus current

35 mA maximum

Power dissipation

5.5W

Thermal dissipation

18.8 BTU/hr maximum

Isolation voltage

250V (continuous), Basic Insulation Type, relay to relay, relay to 
backplane, and relay to power
50V (continuous), Basic Insulation Type, power to backplane

Type tested at 1500V AC for 60 s, relay to relay, all combinations.          
Type tested at 3250V DC for 60 s, relay to backplane and relay to power
Type tested at 900V DC for 60 s, power to backplane. 

Fusing

Fusing of outputs is recommended. Use 3.0 A, 250V AC slow-blow fuses 
(Littelfuse pt. no. 239003).

Indicators

8 yellow status indicators - show status of individual outputs. If relay 
output bit is on, corresponding output indicator is on.

Keyswitch position

9

Terminal screw torque

Determined by installed terminal base 

Dimensions (with module 
installed)

94H x 94W x 69D mm (3.7H x 3.7W x 2.7D inches )

Enclosure

None (open-style)

Wiring category

(1)

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and 
Grounding Guidelines, publication 

1770-4.1.

2 - on signal ports

Wire size

Determined by installed terminal base

Pilot Duty Rating

C300, R150

North American temp code

T4 (1794-OW8XT)

 

T5 (1794-OW8, 1794-OW8K)

IEC Temp Code

T4 (1794-OW8XT)

 

T5 (1794-OW8, 1794-OW8K)

Environmental

Attribute

Value

Operating temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

 

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

 

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

 

0…55 °C (32…131 °F) (1794-OW8, 1794-OW8K)

 

-20…70 °C (-4…158 °F) (1794-OW8XT)

Non-operating 
temperature

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),

 

IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),

 

IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):

 

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

 

5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

 

5 g @ 10…500 Hz

Operating shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

 

12 g

Non-operating shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

 

50 g

Emissions

CISPR 11:

 

Group 1, Class A

ESD immunity

IEC 61000-4-2:

 

6 kV contact discharges

 

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:

 

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz

 

10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz

 

10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz

 

3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:

 

±2 kV at 5 kHz on signal ports

Surge transient 
immunity

IEC 61000-4-5:

 

±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports

Conducted RF immunity

IEC 61000-4-6:

 

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications (when product is marked)

(1)

(1)

See the Product Certification link at 

http://www.ab.com

 for Declaration of Conformity, Certificates, and other 

certification details.

Attribute

Value

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File 
E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. 
and Canada. See UL File E194810.

CSA

(1794-OW8, 1794-OW8K)
CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D 
Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/EC EMC Directive, compliant with:

 

EN 61326-1; Meas./Control/Lab., Industrial Requirements

 

EN 61000-6-2; Industrial Immunity

 

EN 61000-6-4; Industrial Emissions

 

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

 

European Union 2006/95/EC LVD, compliant with:

 

EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with:

 

AS/NZS CISPR 11; Industrial Emissions

Ex 

(1794-OW8XT)
European Union 94/9/EC ATEX Directive, compliant with:

 

EN 60079-15; Potentially Explosive Atmospheres, Protection "n"

 

EN 60079-0; General Requirements

 

II 3 G Ex nA nC IIC T4X

 

when used at or below 60V AC or 75V DC

(1794-OW8, 1794-OW8K)
European Union 94/9/EC ATEX Directive, compliant with:

 

EN 60079-15; Potentially Explosive Atmospheres, Protection "n"

 

EN 60079-0; General Requirements

 

II 3 G Ex nA nC IIC T5X

 

when used at or below 60V AC or 75V DC

TÜV 

(1794-OW8, 1794-OW8K)
TÜV Certified for Functional Safety:
up to and including SIL 2

Summary of Contents for 1794-OW8

Page 1: ...ype ratings that are required to comply with certain product safety certifications In addition to this publication see Industrial Automation Wiring and Grounding Guidelines for additional installation requirements Allen Bradley publication 1770 4 1 NEMA Standards 250 and IEC 60529 as applicable for explanations of the degrees of protection provided by different types of enclosure WARNING When you ...

Page 2: ...orable code de température le plus faible peut être utilisé pour déterminer le code de température global du système Les combinaisons d équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l installation WARNING EXPLOSION HAZARD Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous Do not disconnect con...

Page 3: ...sing 240V power to a relay you must connect a snubber across the load Failure to connect a snubber across the load relay contacts can result in generation of electromagnetic noise which could disrupt nearby electrical equipment including your 1794 FLEX I O chassis Use Allen Bradley part number 599 KA04 or 1401 NX1 ATTENTION Apply only 24V DC power to the power terminals on the terminal base unit M...

Page 4: ... Grounding Guidelines publication 1770 4 1 2 on signal ports Wire size Determined by installed terminal base Pilot Duty Rating C300 R150 North American temp code T4 1794 OW8XT T5 1794 OW8 1794 OW8K IEC Temp Code T4 1794 OW8XT T5 1794 OW8 1794 OW8K Environmental Attribute Value Operating temperature IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb...

Reviews: